Product Introduction

1. Product Overview

  • This soft start controller uses advanced microprocessors as its core, applies advanced software design methods and the latest hardware technology, and adopts thyristor phase-shifting technology to achieve soft start and soft stop functions for AC asynchronous motors. It also has multiple protection functions such as phase failure, overvoltage, undervoltage, overcurrent, overload, three-phase imbalance, and short circuit.

  • This soft starter covers 7.5KW~600KW, with reliable quality and good electromagnetic compatibility (EMC). It can be widely used in heavy-duty equipment such as fans, water pumps, ball mills, crushers, conveyors, and compressors. Before installing or operating this soft starter, please read and understand this manual. Only professionals can provide the ideal replacement product for pressure reducing starting equipment such as diagonal conversion, autotransformer pressure reduction, and magnetic control pressure reduction.


2. Product features

  • Adopting high-performance microcontrollers and digital logic control technology, it has strong anti-interference ability.

  • The startup parameters can be flexibly set according to different loads to achieve the optimal current curve and torque control characteristics.

  • Provides a smooth and gradual starting process for the electric motor, reduces the impact of starting current on the power grid, and lowers equipment vibration and noise,

  • Extended the service life of the mechanical transmission system and improved the working environment for workers.

  • The starting current can be adjusted according to the load to reduce starting losses and generate optimal torque with minimal current.

  • There is no phase sequence requirement for the input power supply.

  • It can be set as free parking and soft parking, with adjustable soft parking time.

  • Comes with standard RS485 interface and Modbus protocol (order declaration).

  • Adopting a 4x8 LCD display, parameter modification and operation are simple and intuitive.

  • The product has a novel structure, reliable performance, strong functionality, and easy installation and operation.


3. Product Application Introduction

  • The product is widely used in various industries such as thermal power generation, hydropower, power transmission and distribution equipment, metallurgy, chemical industry, mining, and construction.

  • The water pump utilizes the soft stop function to alleviate the water hammer phenomenon when stopped, saving the cost of system maintenance.

  • The ball mill utilizes a voltage ramp to start, reducing gear torque wear and maintenance workload, saving both time and expenses.

  • The fan reduces belt wear and mechanical impact, saving maintenance costs.

  • The belt conveyor achieves a smooth and gradual starting process through soft start, avoiding product movement and material spillage.

  • The compressor utilizes current limiting to achieve smooth start-up, reduce motor heating, and extend service life.


4. Usage and environmental conditions

Applicable standard: GB14048.6-2008

Usage category: AC-53A or AC-53B

Rated voltage: 380V+15%, AC three-phase symmetrical power supply: available

Customized soft starters with rated voltages of 220V, 480V, and 660V

Frequency: 50Hz/60Hz+2%

Startup frequency: 12 times/hour

Cooling method: Natural air cooling for soft starter, fan cooling for intelligent soft starter cabinet.

Installation method: wall mounted or cabinet vertical

Protection level: IP00

Operating altitude: 1000 meters without capacity reduction (for every 100 meters increase above 1000 meters, the current decreases by 0.5%)

Environmental temperature: Storage: -25~+70°C

Working temperature: -5℃~+55,40Above, 1 per liter2% reduction in current

Relative humidity: maximum 90% (temperature at 20 ° C)When)

Pollution level: Level III


5. Working principle

The principle block diagram of this soft starter is shown in Figure 2. The power part is composed of three pairs of anti parallel thyristors as shown in Figure 1. The core microprocessor of the control part collects the synchronization signal, voltage signal/current signal, and motor power factor angle of the power grid. The control software applies thyristor phase-shifting technology based on these four parameters to gradually increase the voltage applied to the motor to full voltage according to a certain law. By appropriately setting control parameters, the torque and current of the motor can be well matched with the load requirements.

image


6. Precautions for selecting rows

A soft starter must provide a force greater than the load resistance torque to complete the start. For ordinary loads such as water pumps, fans, etc., it is recommended to configure a soft starter with the same gear specification or a higher gear specification. For heavy loads such as ball machines, 6-stage fans, crushers, etc., it is recommended to configure a soft starter with a higher gear specification or a second gear specification.


External dimensions of soft starter

image


Installation requirements

image

image


Online application wiring diagram

image


image

image

Terminal configuration diagram

(1) Main circuit terminal diagram

image


(2) Terminal diagram of control circuit

image


(3) Control circuit terminal wiring

image


Key interface

image


Functional parameter table

code name scope factory default Instructions address
one hundred starting voltage 25 - 80% thirty Initial starting voltage 0
one hundred and one Acceleration ramp time 0 - 60S ten Voltage acceleration time one
one hundred and two Current limiting multiple 100~500% three hundred and fifty Maximum current percentage during startup process two
one hundred and three Deceleration ramp time 0~30S 0 When set to 0, it is free parking three
one hundred and four Starting curve 0~1 0 0. Voltage ramp
1. Voltage secondary ramp
four
one hundred and five Impulse starting voltage 50~100% eighty Sudden jump voltage value five
one hundred and six Impact start time 0~5S 0 Jump duration six
one hundred and seven Rated current of motor 2 - 2000A - Adapt to the rated current of the motor seven
one hundred and eight grid frequency 0~1 0 0、50HZ 1、60HZ eight
one hundred and nine operating current 70~500% one hundred and fifty Current protection value during operation
=70. Turn off overcurrent protection
nine
one hundred and ten Current imbalance value 10~100% forty =100 turn off phase current imbalance detection ten
one hundred and eleven Start time limit 5 - 80S sixty Maximum start-up time eleven
one hundred and twelve Overload curve 0~4 two 0:10A;1:10;2:20;2:30;4:OFF twelve
one hundred and thirteen High current protection 0~1 0 =0 close=1 open
Starting current exceeding 5.5Ie, duration exceeding 200mS, high current protection
thirteen
one hundred and fourteen phase sequence protection 0~1 0 =0 close=1 open fourteen
one hundred and fifteen Power grid quality 0~2 0 0: Better; 1: Poor; 2: Very bad fifteen
one hundred and sixteen Main circuit protection 0~1 0 =0 close=1 open fifteen
one hundred and seventeen undervoltage 70~100% eighty =Turn off undervoltage protection at 100 hours seventeen
one hundred and eighteen overvoltage 100~130% one hundred and twenty =Close overvoltage protection at 100 hours eighteen
one hundred and nineteen Control selection 0~5 three 0. Keyboard 1. External control 2. Communication 3. Keyboard, external control 4. Keyboard, communication 5. External control, communication 6. Keyboard, external control, communication nineteen
one hundred and twenty Programming input selection 0~1 0 0. Fault reset 1. Instant stop twenty
one hundred and twenty-one Programming output selection 0~5 five 0. Starting process 1. Running 2. Soft stop 3. Starting and running 4. Faults 5. Main circuit faults twenty-one
one hundred and twenty-two Programming output delay 0~30S 0 -- twenty-two
one hundred and twenty-three Mailing Address 1~32 one -- twenty-three
one hundred and twenty-four Baud rate 0~2 one 0.4800 1.9600 2.19200 twenty-four
one hundred and twenty-five user password 0 - 9999 0 -- twenty-five
one hundred and twenty-six Milliampere proportional coefficient 50~150% one hundred -- twenty-six
one hundred and twenty-seven Current proportional coefficient 50~150% one hundred Used to adjust the current display value twenty-seven
one hundred and twenty-eight Password entry 0~65535 0 -- twenty-eight
129~139 Undefined parameters 28 - 29


Fault Code Table and Solutions

name Instructions solution
F01 input phase loss Check the three-phase voltage at the input end
F02 Output phase loss Check if the input motor is securely connected
F03 operating current During operation, the motor experiences overload
F04 Current imbalance There is a deviation in the three-phase current at the output end
F05 The startup time is too long Overloaded, contact the manufacturer
F06 Abnormal frequency Unstable frequency at the power supply end
F07 Reverse power supply sequence Adjust phase sequence
F08 High current fault Overloaded load
F09 Thermal overload Soft start overheating, heat dissipation needs to be strengthened
F10 Parameter loss Contact the manufacturer
F11 Thyristor overheating Shutdown for 30 minutes to dissipate heat
F12 overvoltage The power supply voltage is too high
F13 undervoltage Current and voltage too low
F14 Main circuit malfunction Check the load end and contact the manufacturer