Overview
The destructive power of lightning is extremely strong, and lightning waves can directly or indirectly (through electromagnetic induction) invade various electrical and metal channels (such as power lines, signal lines, and metal pipelines). The lightning overvoltage and surge voltage generated from this will cause great harm to electrical equipment and communication information systems, ranging from damaging power lines to damaging electrical equipment, causing system paralysis and incalculable losses.
HBL1 surge protector is an ideal overvoltage protection device used to protect various electrical equipment in low-voltage power grids from lightning overvoltage and various surge voltages.
principle
The HBL1 type surge protector uses a varistor with excellent nonlinear characteristics, which is connected between the phase line and neutral line (L-N), phase line and ground line (L-PN), and neutral line and ground line (N-PE). Under normal conditions, the surge protector is in a very high resistance state, and the leakage current is almost zero, ensuring the normal power supply of the power system. When the power system experiences overvoltage in the above situation, the surge protector immediately conducts rapidly in nanoseconds, limiting the amplitude of the overvoltage within the safe working range of the equipment and directing the energy of the overvoltage into the ground, thereby protecting the electrical equipment. Subsequently, the surge protector quickly changed to a high resistance state, thus not affecting the normal power supply of the power system.
Technical Features
1. Adopting internal wiring, the overall structure is compact and easy to install and connect.
2. High speed response, action time less than 25ns
3. The working status is clearly displayed in green (normal) and red (faulty).
4. Additional functions can be added, such as sound and light alarm (B), fault remote signaling contact (X)
Classification of Circuit Breakers


HBL1-C series surge protector
Technical Specifications
serial number | Model specification/parameter name | HBL1-C/550 | HBL1-C/385 | HBL1-C/275 | HBL1-C/130 | HBL1-C/75 | |
one | UR rated voltage V (effective value) | three hundred and eighty | two hundred and twenty | one hundred and ten | sixty | thirty-six | |
two | UO maximum continuous operating voltage V (effective value) | three hundred and fifty | three hundred and eighty-five | two hundred and seventy-five | one hundred and thirty | seventy-five | |
three | U1NA pressure-sensitive voltage V | nine hundred and ten | three hundred and eighty-five | four hundred and thirty | two hundred | one hundred and twenty | |
four | ISC nominal discharge current KA (8/20 μ s) | twenty | twenty | twenty | twenty | ten | |
five | ISC maximum discharge current KA (8/20 μ s) | forty | forty | forty | forty | twenty | |
six | Up protection level (Residual voltage value under corresponding current) KVIs=1kv | Is=1kv | one point one | zero point eight | zero point two four | zero point zero eight | zero point zero seven |
seven | Is=5kv | one point three | one | zero point three | zero point one | zero point one | |
eight | Is=10kv | one point six | one point one | zero point four | zero point two | zero point one five | |
nine | Is=15kv | one point seven | one point two | zero point six | zero point three | zero point two | |
ten | Is=20kv | one point seven eight zero | one point two two five | zero point eight six zero | zero point four zero zero | zero point two four zero | |
eleven | Is=40kv | one point nine zero | one point five zero | zero point nine zero | zero point four five zero | zero point three four zero | |
twelve | Is=60kv | ||||||
thirteen | WF energy tolerance A (2ms) | two hundred | |||||
fourteen | Corresponding time t (ns) | ≤25 | |||||
fifteen | IC leakage current μ A | <9 | |||||
sixteen | Installation type | 35mm standard track | |||||
seventeen | housing material | Flame retardant reinforced PA66 | |||||
eighteen | Size mm | 90X72X60 (4 pieces) 90X36X60 (2 pieces) 90X54X60 (3 pieces) | |||||
Appearance and installation dimensions
HBL1 surge protector is used for low-voltage AC power supply in single-phase systems (phase line L+neutral line N), three-phase three wire (three wire 3L), and three-phase four wire (three wire 3L+neutral line N) systems, to protect their electrical equipment from lightning overvoltage voltage and various surge voltages. (Therefore, the product name is surge protector) The specific usage reference is as follows:
One pole (one module), used for 220V single line systems, with its neutral and ground wires directly connected. (L-NPE)
Two poles (two module combination) for 220V single-phase systems (L-PE, N-PE)
3-pole (three module combination) for 380V three-phase three wire system (L1-PE, L2-PE, L3-PE)
Four poles (four modules) are used for 380V/220V three-phase four wire systems (L-PE, L2-PE, L3-PE, N-PE, TN systems) (L-PE, L2-PE, L3-PE, N-PE, TT systems)
Note: L: Phase line N: Neutral line PE: Ground line
When the surge protector is working normally, the indicator sign is green. After the failure of the gear module, the indicator will turn red. The lightning arrester with sound and light alarm function will emit a buzzing sound and display a red light when the module fails. Remote signaling function: When the module fails, the alarm will emit a buzzing sound and also send out contact signals for closing and opening for remote monitoring. After the module fails, it needs to be replaced immediately. To maintain the normal operation of the surge protector, it should be tested every six months and replaced immediately if it is found to be ineffective.


400-0577-818
Consultation HotlineMobile Site
Copyright © 2025 China · Huabang Power Technology Co., Ltd. All rights reserved.