Huabang Power Technology Co., Ltd.

National Unified Hotline: 400-0577-818

EN
Position: Index>Products>Meter Box Series > HBL1-C series

HBL1-C series surge protector

HBL1-C series

Overview

The destructive power of lightning is extremely strong, and lightning waves can directly or indirectly (through electromagnetic induction) invade various electrical and metal channels (such as power lines, signal lines, and metal pipelines). The lightning overvoltage and surge voltage generated from this will cause great harm to electrical equipment and communication information systems, ranging from damaging power lines to damaging electrical equipment, causing system paralysis and incalculable losses.

HBL1 surge protector is an ideal overvoltage protection device used to protect various electrical equipment in low-voltage power grids from lightning overvoltage and various surge voltages.


principle

The HBL1 type surge protector uses a varistor with excellent nonlinear characteristics, which is connected between the phase line and neutral line (L-N), phase line and ground line (L-PN), and neutral line and ground line (N-PE). Under normal conditions, the surge protector is in a very high resistance state, and the leakage current is almost zero, ensuring the normal power supply of the power system. When the power system experiences overvoltage in the above situation, the surge protector immediately conducts rapidly in nanoseconds, limiting the amplitude of the overvoltage within the safe working range of the equipment and directing the energy of the overvoltage into the ground, thereby protecting the electrical equipment. Subsequently, the surge protector quickly changed to a high resistance state, thus not affecting the normal power supply of the power system.


Technical Features

1. Adopting internal wiring, the overall structure is compact and easy to install and connect.

2. High speed response, action time less than 25ns

3. The working status is clearly displayed in green (normal) and red (faulty).

4. Additional functions can be added, such as sound and light alarm (B), fault remote signaling contact (X)


Classification of Circuit Breakers

image

HBL1-C series surge protector


    Technical Specifications


serial number

Model specification/parameter name

HBL1-C/550

HBL1-C/385

HBL1-C/275

HBL1-C/130

HBL1-C/75

one

UR rated voltage V (effective value)

three hundred and eighty

two hundred and twenty

one hundred and ten

sixty

thirty-six

two

UO maximum continuous operating voltage V (effective value)

three hundred and fifty

three hundred and eighty-five

two hundred and seventy-five

one hundred and thirty

seventy-five

three

U1NA pressure-sensitive voltage V

nine hundred and ten

three hundred and eighty-five

four hundred and thirty

two hundred

one hundred and twenty

four

ISC nominal discharge current KA (8/20 μ s)

twenty

twenty

twenty

twenty

ten

five

ISC maximum discharge current KA (8/20 μ s)

forty

forty

forty

forty

twenty

six



Up protection level

(Residual voltage value under corresponding current)

KVIs=1kv

Is=1kv

one point one

zero point eight

zero point two four

zero point zero eight

zero point zero seven

seven

Is=5kv

one point three

one

zero point three

zero point one

zero point one

eight

Is=10kv

one point six

one point one

zero point four

zero point two

zero point one five

nine

Is=15kv

one point seven

one point two

zero point six

zero point three

zero point two

ten

Is=20kv

one point seven eight zero

one point two two five

zero point eight six zero

zero point four zero zero

zero point two four zero

eleven

Is=40kv

one point nine zero

one point five zero

zero point nine zero

zero point four five zero

zero point three four zero

twelve

Is=60kv






thirteen

WF energy tolerance A (2ms)

two hundred

fourteen

Corresponding time t (ns)

≤25

fifteen

IC leakage current μ A

<9

sixteen

Installation type

35mm standard track

seventeen

housing material

Flame retardant reinforced PA66

eighteen

Size mm

90X72X60 (4 pieces) 90X36X60 (2 pieces) 90X54X60 (3 pieces)



    Appearance and installation dimensions

HBL1 surge protector is used for low-voltage AC power supply in single-phase systems (phase line L+neutral line N), three-phase three wire (three wire 3L), and three-phase four wire (three wire 3L+neutral line N) systems, to protect their electrical equipment from lightning overvoltage voltage and various surge voltages. (Therefore, the product name is surge protector) The specific usage reference is as follows:

One pole (one module), used for 220V single line systems, with its neutral and ground wires directly connected. (L-NPE)

Two poles (two module combination) for 220V single-phase systems (L-PE, N-PE)

3-pole (three module combination) for 380V three-phase three wire system (L1-PE, L2-PE, L3-PE)

Four poles (four modules) are used for 380V/220V three-phase four wire systems (L-PE, L2-PE, L3-PE, N-PE, TN systems) (L-PE, L2-PE, L3-PE, N-PE, TT systems)

Note: L: Phase line N: Neutral line PE: Ground line

When the surge protector is working normally, the indicator sign is green. After the failure of the gear module, the indicator will turn red. The lightning arrester with sound and light alarm function will emit a buzzing sound and display a red light when the module fails. Remote signaling function: When the module fails, the alarm will emit a buzzing sound and also send out contact signals for closing and opening for remote monitoring. After the module fails, it needs to be replaced immediately. To maintain the normal operation of the surge protector, it should be tested every six months and replaced immediately if it is found to be ineffective.

imageimage


Hotline

400-0577-818

Consultation Hotline
二维码

Mobile Site

Copyright © 2025 China · Huabang Power Technology Co., Ltd. All rights reserved.

ICP: 浙ICP备09083223号-8

Powered by: wzzw.com