Position: Index>Products>YBQY Series > 185-220KW

185-220KW Online soft start

185-220KW

Overview

This soft start controller uses advanced microprocessors as its core, applies advanced software design methods and the latest hardware technology, and adopts thyristor phase-shifting technology to achieve soft start and soft stop functions for AC asynchronous motors. It also has multiple protection functions such as phase failure, overvoltage, undervoltage, overcurrent, overload, three-phase imbalance, and short circuit.

This soft starter covers 7.5KW~600KW, with reliable quality and good electromagnetic compatibility (EMC). It can be widely used in heavy-duty equipment such as fans, water pumps, ball mills, crushers, conveyors, and compressors. Before installing or operating this soft starter, please read and understand this manual. Only professionals can provide the ideal replacement product for pressure reducing starting equipment such as diagonal conversion, autotransformer pressure reduction, and magnetic control pressure reduction.


1. The soft starter has the following characteristics

  • Adopting high-performance microcontrollers and digital logic control technology, it has strong anti-interference ability.

  • The startup parameters can be flexibly set according to different loads to achieve the optimal current curve and torque control characteristics.

  • It provides a smooth and gradual starting process for the electric motor, reduces the impact of starting current on the power grid, lowers equipment vibration and noise, prolongs the service life of the mechanical transmission system, and improves the working environment for workers. The starting current can be adjusted according to the load to reduce starting losses and generate optimal torque with minimal current.

  • There is no phase sequence requirement for the input power supply.

  • It can be set as free parking and soft parking, with adjustable soft parking time.

  • Comes with standard RS485 interface and Modbus protocol (order declaration).

  • Adopting a 4x8 LCD display, parameter modification and operation are simple and intuitive.

  • The product has a novel structure, reliable performance, strong functionality, and easy installation and operation.


2. Structural characteristics

  • Intelligent soft starter: naturally air-cooled, external AC contactor. Online soft starter, no need for external AC contactor.

  • Intelligent starter cabinet: exquisite structure and simple installation.


3. Introduction to Typical Applications of the Product

  • The product is widely used in various industries such as thermal power generation, hydropower, power transmission and distribution equipment, metallurgy, chemical industry, mining, and construction.

  • The water pump utilizes the soft stop function to alleviate the water hammer phenomenon when stopped, saving the cost of system maintenance.

  • The ball mill utilizes a voltage ramp to start, reducing gear torque wear and maintenance workload, saving both time and expenses.

  • The fan reduces belt wear and mechanical impact, saving maintenance costs.

  • The compressor utilizes current limiting to achieve smooth start-up, reduce motor heating, and extend service life. The belt conveyor achieves a smooth and gradual starting process through soft start, avoiding product movement and material spillage.


4. Usage and environmental conditions

  • Applicable standard: GB14048.6-2008

  • Usage category: AC-53A or AC-53B

  • Rated voltage: 380V ± 15%, AC three-phase symmetrical power supply; Customizable soft starters with rated voltages of 220V, 480V, and 660V

  • Frequency: 50Hz/60Hz ± 2%

  • Startup frequency: 12 times/hour

  • Cooling method: Natural air cooling for soft starter, fan cooling for intelligent soft starter cabinet.

  • Installation method: wall mounted or cabinet vertical

  • Protection level: IP00

  • Operating altitude: 1000 meters without capacity reduction (for every 100 meters increase above 1000 meters, the current decreases by 0.5%)

  • Environmental temperature: Storage: -25 ℃~+70 ℃

  • Working temperature: -5 ℃~+55 ℃, above 40 ℃, with a 2% decrease in current per liter of 1 ℃

  • Relative humidity: maximum 90% (at a temperature of 20 ℃)

  • Pollution level: Shh level


5. Packaging Content

  • a. Soft starter/cabinet

  • b. User Manual

  • c. Certificate of Conformity


6. Working principle

The principle block diagram of this soft starter is shown in Figure 2. The power part is composed of three pairs of anti parallel thyristors as shown in Figure 1. The core microprocessor of the control part collects the synchronization signal, voltage signal, current signal, and motor power factor angle of the power grid. The control software applies thyristor phase-shifting technology based on the changes of these four parameters to gradually increase the voltage applied to the motor to full voltage according to a certain law. By appropriately setting control parameters, the torque and current of the motor can be well matched with the load requirements.


image


7. Purchase inspection

  • Before removing the soft starter from its packaging material, please confirm that the packaging cardboard box has not been damaged during transportation. The damage to packaging cartons is usually caused by improper transportation. If any damage is found, please notify the carrier and your distributor representative.

  • Please confirm that the nameplate and label of the soft starter comply with the packaging list and corresponding purchase order. If the soft starter is not installed immediately, it should be stored in a clean and dry area with an ambient temperature of -25 ℃~+70 ℃.


Product Selection

1. Product nameplate

image


2. Model meaning

image


3. Selection precautions

Soft starters must provide a force greater than the load resistance torque to complete the start-up. For ordinary loads such as water pumps, fans, etc., it is recommended to configure soft starters with the same or higher gear specifications. For heavy loads such as ball mills, 6-stage fans, crushers, etc., it is recommended to configure soft starters with higher or second gear specifications.


install

1. External dimensions of soft starter

① 0.75KW heavy~75KW light (Figure 311)

image


② 75KW heavy~800KW light (Figure 312)

image



image


2. Installation requirements

Installation direction

① Be sure to install the soft starter in a vertical direction, do not invert it, and use screws to install it on a sturdy structure.

② When the soft starter operates, it generates heat. To ensure the flow of air, it should be as shown in Figure 3.2. Leave some space in the design. Generate heat and dissipate it upwards, so do not install it under heat-resistant equipment.

③ The main circuit adopts upper and lower outlets, and the wires should ensure sufficient current carrying capacity.


image


wiring

1. Application wiring diagram

Dimensions of online soft starter

image


Terminal configuration diagram

(1) Main circuit terminal diagram

image


(2) Terminal diagram of control circuit

image


(3) Control circuit terminal wiring

image


Online soft starter primary and secondary line diagram

image


Bypass type soft starter primary and secondary wiring diagram

image


Display keyboard interface

1. Display keyboard instructions

image


2. Buttons

Button name Functional Description

image

  • 1. In the ready state, press the 【 Confirm 】 key to enter the help menu, and then press the 【 Confirm 】 key to exit. You can also press the 'Stop/Reset' button to exit.

  • 2. In the setting state, press the 【 Confirm 】 key to save the new data and exit the setting state.

image

  • 1. In the ready state, press the 【 Settings 】 key to enter the function help menu, which displays' User Parameters: XXX '; At this point, press the 【▲】【 ▼ 】 keys to display the next (upper) parameter value.

  • 2. Press the 【 Settings 】 key again to enter the settings mode, and the colon will flash. At this time, you can use the 【 ▲】【 ▼ 】 keys to modify the parameter values after the colon. Press the [Confirm] key when the colon flashes. If the data has been modified, it means that the new data has been saved, and then exit. If you do not want to save new data, press the 【 Settings 】 key to stop the colon flashing and restore the original data, then press the 【 Confirm 】 key to exit.

image

  • 1. In the settings menu, when the colon is not flashing, press the 【 ▲】 and 【 ▼ 】 keys to change the function number; When the colon flashes, press the [▲] and [▼] keys to change the data. Hold down the [▲] and [▼] keys for more than 1 second, and the data will quickly and continuously increase or decrease.

  • 2. Press the [▲] and [▼] keys in the help menu to change the corresponding help prompt information content.

image

  • The motor can only be started when the 119 function parameter setting keyboard is valid. Otherwise, this key cannot start the motor

image

  • When the function parameter 119 is set to be valid, the keyboard can only be stopped. Otherwise, pressing this key will not stop the machine. Long pressing in the fault state will activate the "reset" function.


3. Function parameter table

code name scope factory default Instructions address
one hundred starting voltage 25 - 80% forty Initial starting voltage 0
one hundred and one Acceleration ramp time 0 - 60S ten Voltage acceleration time one
one hundred and two Current limiting multiple 100~500% three hundred and fifty Maximum current percentage during startup process two
one hundred and three Deceleration ramp time 0~30S 0 When set to 0, it is free parking three
one hundred and four Starting curve 0~1 0 0. Voltage ramp
1. Voltage secondary ramp
four
one hundred and five Impulse starting voltage 50~100% eighty Sudden jump voltage value five
one hundred and six Impact start time 0~5S 0 Jump duration six
one hundred and seven Rated current of motor 2 - 2000A - Adapt to the rated current of the motor seven
one hundred and eight grid frequency 0 - 1 0 0、50HZ 1、60HZ eight
one hundred and nine operating current 70~500% one hundred and fifty The fan and water pump are equipped with 100
The crusher is equipped with 150
nine
one hundred and ten Current imbalance value 10~100% forty =100 turn off current imbalance detection ten
one hundred and eleven Start time limit 5 - 80S sixty Maximum start-up time eleven
one hundred and twelve Overload curve 0 - 4 two 0:10A;1:10;2:20;3:30;4:OFF twelve
one hundred and thirteen High current protection 0 - 1 0 =0 close=1 open
Starting current exceeding 5.5Ie, duration exceeding 200mS, high current protection
thirteen
one hundred and fourteen phase sequence protection 0 - 1 0 =0 close=1 open fourteen
one hundred and fifteen Power grid quality 0 - 2 two =0 is better; 1. Poor; 2 is very poor fifteen
one hundred and sixteen Main circuit protection 0 - 1 0 =0 close=1 open
one hundred and seventeen undervoltage 70~100% eighty =Turn off undervoltage protection at 100 hours seventeen
one hundred and eighteen overvoltage 100~130% one hundred and twenty =Close overvoltage protection at 100 hours eighteen
one hundred and nineteen Control selection 0 - 5 three 0 Keyboard 1 External Control 2 Communication 3 Keyboard, External Control 4 Keyboard, Communication 5 External Control, Communication 6 Keyboard, External Control, Communication nineteen
one hundred and twenty Programming input selection 0 - 1 0 0. Fault reset 1. Instant stop twenty
one hundred and twenty-one Programming output selection 0 - 5 five 0. Starting process 1. Operation 2. Soft stop 3. Starting and operation 4. Fault 5. Main circuit fault twenty-one
one hundred and twenty-two Programming output delay 0~30S 0 -- twenty-two
one hundred and twenty-three Mailing Address 1~32 one -- twenty-three
one hundred and twenty-four Baud rate 0 - 2 one 0.4800 1.9600 2.19200 twenty-four
one hundred and twenty-five user password 0 - 9999 0 -- twenty-five
one hundred and twenty-six Milliampere proportional coefficient 50~150% one hundred twenty-six
one hundred and twenty-seven Current proportional coefficient 50~150% one hundred Used to adjust the current display value twenty-seven
one hundred and twenty-eight Password entry 0~65535 0 twenty-eight
129~139 Undefined parameters 28 - 29


Fault Code Table and Solutions

name Instructions solution
F01 input phase loss Check the three-phase voltage at the input end
F02 Output phase loss Check if the input motor is securely connected
F03 operating current During operation, the motor experiences overload
F04 Current imbalance There is a deviation in the three-phase current at the output end
F05 The startup time is too long Overloaded, contact the manufacturer
F06 Abnormal frequency Unstable frequency at the power supply end
F07 Reverse power supply sequence Adjust phase sequence
F08 High current fault Overloaded load
F09 Thermal overload Soft start overheating, heat dissipation needs to be strengthened
F10 Parameter loss Contact the manufacturer
F11 Thyristor overheating Shutdown for 30 minutes to dissipate heat
F12 overvoltage The power supply voltage is too high
F13 undervoltage Current and voltage too low
F14 Main circuit malfunction Check the load end and contact the manufacturer


Safety precautions

safety

  • Before installing or operating this soft starter, please read and understand this manual. Only professionals can install/repair and maintain the soft starter.

  • Installation and maintenance operations should strictly follow this manual, relevant national standards, and industry practices. Otherwise, the manufacturer shall not be responsible for any adverse consequences caused by failure to operate in accordance with the corresponding guidance specifications.

  • Before maintaining the soft starter or motor, all power inputs must be disconnected.

  • After installation, carefully inspect and verify that no parts (such as wire ends, screws, washers, etc.) have fallen into the live parts.


Warning

  • The control part of this product (including the triggering unit and the central processing unit control part) is equipped with dangerous voltage. The triggering unit has the same high voltage as the main circuit. If it is illegally touched, it will be very dangerous and may cause electric shock accidents.

  • After connecting this product to the main power supply, even if the control voltage is disconnected or the starter is stopped, a full voltage signal for sampling will still appear at the output terminal of the soft starter.

  • The product must be well grounded to ensure safe normal operation and prevent accidental electric shock injuries. Do not connect power factor compensation capacitors to the output terminal of the soft starter.