Overview
This soft start controller uses advanced microprocessors as its core, applies advanced software design methods and the latest hardware technology, and adopts thyristor phase-shifting technology to achieve soft start and soft stop functions for AC asynchronous motors. It also has multiple protection functions such as phase failure, overvoltage, undervoltage, overcurrent, overload, three-phase imbalance, and short circuit.
This soft starter covers 7.5KW~600KW, with reliable quality and good electromagnetic compatibility (EMC). It can be widely used in heavy-duty equipment such as fans, water pumps, ball mills, crushers, conveyors, and compressors. Before installing or operating this soft starter, please read and understand this manual. Only professionals can provide the ideal replacement product for pressure reducing starting equipment such as diagonal conversion, autotransformer pressure reduction, and magnetic control pressure reduction.
1. The soft starter has the following characteristics
Adopting high-performance microcontrollers and digital logic control technology, it has strong anti-interference ability.
The startup parameters can be flexibly set according to different loads to achieve the optimal current curve and torque control characteristics.
It provides a smooth and gradual starting process for the electric motor, reduces the impact of starting current on the power grid, lowers equipment vibration and noise, prolongs the service life of the mechanical transmission system, and improves the working environment for workers. The starting current can be adjusted according to the load to reduce starting losses and generate optimal torque with minimal current.
There is no phase sequence requirement for the input power supply.
It can be set as free parking and soft parking, with adjustable soft parking time.
Comes with standard RS485 interface and Modbus protocol (order declaration).
Adopting a 4x8 LCD display, parameter modification and operation are simple and intuitive.
The product has a novel structure, reliable performance, strong functionality, and easy installation and operation.
2. Structural characteristics
Intelligent soft starter: naturally air-cooled, external AC contactor. Online soft starter, no need for external AC contactor.
Intelligent starter cabinet: exquisite structure and simple installation.
3. Introduction to Typical Applications of the Product
The product is widely used in various industries such as thermal power generation, hydropower, power transmission and distribution equipment, metallurgy, chemical industry, mining, and construction.
The water pump utilizes the soft stop function to alleviate the water hammer phenomenon when stopped, saving the cost of system maintenance.
The ball mill utilizes a voltage ramp to start, reducing gear torque wear and maintenance workload, saving both time and expenses.
The fan reduces belt wear and mechanical impact, saving maintenance costs.
The compressor utilizes current limiting to achieve smooth start-up, reduce motor heating, and extend service life. The belt conveyor achieves a smooth and gradual starting process through soft start, avoiding product movement and material spillage.
4. Usage and environmental conditions
Applicable standard: GB14048.6-2008
Usage category: AC-53A or AC-53B
Rated voltage: 380V ± 15%, AC three-phase symmetrical power supply; Customizable soft starters with rated voltages of 220V, 480V, and 660V
Frequency: 50Hz/60Hz ± 2%
Startup frequency: 12 times/hour
Cooling method: Natural air cooling for soft starter, fan cooling for intelligent soft starter cabinet.
Installation method: wall mounted or cabinet vertical
Protection level: IP00
Operating altitude: 1000 meters without capacity reduction (for every 100 meters increase above 1000 meters, the current decreases by 0.5%)
Environmental temperature: Storage: -25 ℃~+70 ℃
Working temperature: -5 ℃~+55 ℃, above 40 ℃, with a 2% decrease in current per liter of 1 ℃
Relative humidity: maximum 90% (at a temperature of 20 ℃)
Pollution level: Shh level
5. Packaging Content
a. Soft starter/cabinet
b. User Manual
c. Certificate of Conformity
6. Working principle
The principle block diagram of this soft starter is shown in Figure 2. The power part is composed of three pairs of anti parallel thyristors as shown in Figure 1. The core microprocessor of the control part collects the synchronization signal, voltage signal, current signal, and motor power factor angle of the power grid. The control software applies thyristor phase-shifting technology based on the changes of these four parameters to gradually increase the voltage applied to the motor to full voltage according to a certain law. By appropriately setting control parameters, the torque and current of the motor can be well matched with the load requirements.
7. Purchase inspection
Before removing the soft starter from its packaging material, please confirm that the packaging cardboard box has not been damaged during transportation. The damage to packaging cartons is usually caused by improper transportation. If any damage is found, please notify the carrier and your distributor representative.
Please confirm that the nameplate and label of the soft starter comply with the packaging list and corresponding purchase order. If the soft starter is not installed immediately, it should be stored in a clean and dry area with an ambient temperature of -25 ℃~+70 ℃.
Product Selection
1. Product nameplate
2. Model meaning
3. Selection precautions
Soft starters must provide a force greater than the load resistance torque to complete the start-up. For ordinary loads such as water pumps, fans, etc., it is recommended to configure soft starters with the same or higher gear specifications. For heavy loads such as ball mills, 6-stage fans, crushers, etc., it is recommended to configure soft starters with higher or second gear specifications.
install
1. External dimensions of soft starter
① 0.75KW heavy~75KW light (Figure 311)
② 75KW heavy~800KW light (Figure 312)
2. Installation requirements
Installation direction
① Be sure to install the soft starter in a vertical direction, do not invert it, and use screws to install it on a sturdy structure.
② When the soft starter operates, it generates heat. To ensure the flow of air, it should be as shown in Figure 3.2. Leave some space in the design. Generate heat and dissipate it upwards, so do not install it under heat-resistant equipment.
③ The main circuit adopts upper and lower outlets, and the wires should ensure sufficient current carrying capacity.
wiring
1. Application wiring diagram
Dimensions of online soft starter
Terminal configuration diagram
(1) Main circuit terminal diagram
(2) Terminal diagram of control circuit
(3) Control circuit terminal wiring
Online soft starter primary and secondary line diagram
Bypass type soft starter primary and secondary wiring diagram
Display keyboard interface
1. Display keyboard instructions
2. Buttons
| Button name | Functional Description |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3. Function parameter table
| code | name | scope | factory default | Instructions | address |
| one hundred | starting voltage | 25 - 80% | forty | Initial starting voltage | 0 |
| one hundred and one | Acceleration ramp time | 0 - 60S | ten | Voltage acceleration time | one |
| one hundred and two | Current limiting multiple | 100~500% | three hundred and fifty | Maximum current percentage during startup process | two |
| one hundred and three | Deceleration ramp time | 0~30S | 0 | When set to 0, it is free parking | three |
| one hundred and four | Starting curve | 0~1 | 0 | 0. Voltage ramp 1. Voltage secondary ramp |
four |
| one hundred and five | Impulse starting voltage | 50~100% | eighty | Sudden jump voltage value | five |
| one hundred and six | Impact start time | 0~5S | 0 | Jump duration | six |
| one hundred and seven | Rated current of motor | 2 - 2000A | - | Adapt to the rated current of the motor | seven |
| one hundred and eight | grid frequency | 0 - 1 | 0 | 0、50HZ 1、60HZ | eight |
| one hundred and nine | operating current | 70~500% | one hundred and fifty | The fan and water pump are equipped with 100 The crusher is equipped with 150 |
nine |
| one hundred and ten | Current imbalance value | 10~100% | forty | =100 turn off current imbalance detection | ten |
| one hundred and eleven | Start time limit | 5 - 80S | sixty | Maximum start-up time | eleven |
| one hundred and twelve | Overload curve | 0 - 4 | two | 0:10A;1:10;2:20;3:30;4:OFF | twelve |
| one hundred and thirteen | High current protection | 0 - 1 | 0 | =0 close=1 open Starting current exceeding 5.5Ie, duration exceeding 200mS, high current protection |
thirteen |
| one hundred and fourteen | phase sequence protection | 0 - 1 | 0 | =0 close=1 open | fourteen |
| one hundred and fifteen | Power grid quality | 0 - 2 | two | =0 is better; 1. Poor; 2 is very poor | fifteen |
| one hundred and sixteen | Main circuit protection | 0 - 1 | 0 | =0 close=1 open | |
| one hundred and seventeen | undervoltage | 70~100% | eighty | =Turn off undervoltage protection at 100 hours | seventeen |
| one hundred and eighteen | overvoltage | 100~130% | one hundred and twenty | =Close overvoltage protection at 100 hours | eighteen |
| one hundred and nineteen | Control selection | 0 - 5 | three | 0 Keyboard 1 External Control 2 Communication 3 Keyboard, External Control 4 Keyboard, Communication 5 External Control, Communication 6 Keyboard, External Control, Communication | nineteen |
| one hundred and twenty | Programming input selection | 0 - 1 | 0 | 0. Fault reset 1. Instant stop | twenty |
| one hundred and twenty-one | Programming output selection | 0 - 5 | five | 0. Starting process 1. Operation 2. Soft stop 3. Starting and operation 4. Fault 5. Main circuit fault | twenty-one |
| one hundred and twenty-two | Programming output delay | 0~30S | 0 | -- | twenty-two |
| one hundred and twenty-three | Mailing Address | 1~32 | one | -- | twenty-three |
| one hundred and twenty-four | Baud rate | 0 - 2 | one | 0.4800 1.9600 2.19200 | twenty-four |
| one hundred and twenty-five | user password | 0 - 9999 | 0 | -- | twenty-five |
| one hundred and twenty-six | Milliampere proportional coefficient | 50~150% | one hundred | twenty-six | |
| one hundred and twenty-seven | Current proportional coefficient | 50~150% | one hundred | Used to adjust the current display value | twenty-seven |
| one hundred and twenty-eight | Password entry | 0~65535 | 0 | 28 | |
| 129~139 | Undefined parameters | 28 - 29 |
Fault Code Table and Solutions
| name | Instructions | solution |
| F01 | input phase loss | Check the three-phase voltage at the input end |
| F02 | Output phase loss | Check if the input motor is securely connected |
| F03 | operating current | During operation, the motor experiences overload |
| F04 | Current imbalance | There is a deviation in the three-phase current at the output end |
| F05 | The startup time is too long | Overloaded, contact the manufacturer |
| F06 | Abnormal frequency | Unstable frequency at the power supply end |
| F07 | Reverse power supply sequence | Adjust phase sequence |
| F08 | High current fault | Overloaded load |
| F09 | Thermal overload | Soft start overheating, heat dissipation needs to be strengthened |
| F10 | Parameter loss | Contact the manufacturer |
| F11 | Thyristor overheating | Shutdown for 30 minutes to dissipate heat |
| F12 | overvoltage | The power supply voltage is too high |
| F13 | undervoltage | Current and voltage too low |
| F14 | Main circuit malfunction | Check the load end and contact the manufacturer |
Safety precautions
safety
Before installing or operating this soft starter, please read and understand this manual. Only professionals can install/repair and maintain the soft starter.
Installation and maintenance operations should strictly follow this manual, relevant national standards, and industry practices. Otherwise, the manufacturer shall not be responsible for any adverse consequences caused by failure to operate in accordance with the corresponding guidance specifications.
Before maintaining the soft starter or motor, all power inputs must be disconnected.
After installation, carefully inspect and verify that no parts (such as wire ends, screws, washers, etc.) have fallen into the live parts.
Warning
The control part of this product (including the triggering unit and the central processing unit control part) is equipped with dangerous voltage. The triggering unit has the same high voltage as the main circuit. If it is illegally touched, it will be very dangerous and may cause electric shock accidents.
After connecting this product to the main power supply, even if the control voltage is disconnected or the starter is stopped, a full voltage signal for sampling will still appear at the output terminal of the soft starter.
The product must be well grounded to ensure safe normal operation and prevent accidental electric shock injuries. Do not connect power factor compensation capacitors to the output terminal of the soft starter.