Safety precautions
Do not grip the front cover or terminal cover when handling the frequency converter. If only the front cover is grasped, it will cause the main body to fall off, posing a risk of injury;
When operating the frequency converter, please follow the steps specified for electrostatic discharge (ESD) prevention measures. Otherwise, the internal circuit of the frequency converter may be damaged due to static electricity.


1. Nameplate and model

image

Figure 1-1 Product Naming and Nameplate Identification


Three phase 380V~480V, 37G and below have built-in braking units.


2. Inverter model and technical data

Inverter modelPower capacity KVAInput current AOutput current AAdapted motor
KWHP
Single phase power supply: 220V (-10%~+15), 50/60Hz
VXXX-R40G1onefive point fourtwo point threezero point fourzero point five
VXXX-R70G1one point fiveeight point twofourzero point seven fiveone
VXXX-1R5G1threefourteensevenone point fivetwo
VXXX-2R2G1fourtwenty-threenine point sixtwo point twothree
Three phase power supply: 220V (-10%~+15), 50/60Hz
VXXX-R40G2one point fivethree point fourtwo point onezero point fourzero point five
VXXX-R75G2threefivethree point eightzero point seven fiveone
VXXX-1R5G2fourfive point eightfive point oneone point fivetwo
VXXX-2R2G2five point nineten point fiveninetwo point twothree
VXXX-4R0G2eight point ninefourteen point sixthirteenthree point sevenfive
VXXX-5R5G2seventeentwenty-sixtwenty-fivefive point fiveseven point five
VXXX-7R5G2twenty-onethirty-fivethirty-twoseven point fiveten
VXXX-011G2thirtyforty-six point fiveforty-fiveelevenfifteen
VXXX-015G2fortysixty-twosixtyfifteentwenty
VXXX-018G2fifty-sevenseventy-sixseventy-fiveeighteen point fivetwenty-five
VXXX-022G2sixty-nineninety-twoninety-onetwenty-twothirty
VXXX-030G2eighty-fiveone hundred and thirteenone hundred and twelvethirtyforty
VXXX-2T37Gone hundred and fourteenone hundred and fifty-sevenone hundred and fiftythirty-sevenfifty
Three phase power supply: 380V (-10%~+15), 50/60Hz
VXXX-1R5G4threefivethree point eightone point fivetwo
VXXX-2R2G4fourfive point eightfive point onetwo point twothree
VXXX-3R0G4fiveeightseven point twothreefour
VXXX-4R0G4five point nineten point fiveninefourfive
VXXX-5R5G4eight point ninefourteen point sixthirteenfive point fiveseven point five
VXXX-7R5G4eleventwenty point fiveseventeenseven point fiveten
VXXX-011G4seventeentwenty-sixtwenty-fiveelevenfifteen
VXXX-015G4twenty-onethirty-fivethirty-twofifteentwenty
VXXX-018G4twenty-fourthirty-eight point fivethirty-seveneighteen point fivetwenty-five
VXXX-022G4thirtyforty-six point fiveforty-fivetwenty-twothirty
VXXX-030G4fifty-fourfifty-sevensixtythirtyforty
VXXX-037G4sixty-threesixty-nineseventy-fivethirty-sevenfifty
VXXX-045G4eighty-oneeighty-nineninety-oneforty-fivesixty
VXXX-055G4ninety-sevenone hundred and sixone hundred and twelvefifty-fiveseventy-five
VXXX-075G4one hundred and twenty-sevenone hundred and thirty-nineone hundred and fiftyseventy-fiveone hundred
VXXX-090G4one hundred and fiftyone hundred and sixty-fourone hundred and seventy-sixninetyone hundred and twenty
VXXX-110G4one hundred and seventy-nineone hundred and ninety-sixtwo hundred and tenone hundred and tenone hundred and fifty
VXXX-132G4two hundred and twentytwo hundred and fortytwo hundred and fifty-threeone hundred and thirty-twoone hundred and eighty
VXXX-160G4two hundred and sixty-threetwo hundred and eighty-seventhree hundred and fourone hundred and sixtytwo hundred and ten
VXXX-185G4three hundred and fivethree hundred and twenty-threethree hundred and fortyone hundred and eighty-fivetwo hundred and forty
VXXX-200G4three hundred and thirty-fourthree hundred and sixty-fivethree hundred and seventy-seventwo hundredtwo hundred and sixty
VXXX-220G4three hundred and seventy-fivefour hundred and tenfour hundred and twenty-sixtwo hundred and twentytwo hundred and eighty-five
VXXX-250G4four hundred and fourfour hundred and forty-onefour hundred and sixty-fivetwo hundred and fiftythree hundred and twenty
VXXX-280G4four hundred and fifty-threefour hundred and ninety-fivefive hundred and twentytwo hundred and eightythree hundred and seventy
VXXX-315G4five hundred and seventeenfive hundred and sixty-fivefive hundred and eighty-fivethree hundred and fifteenfour hundred and twenty
VXXX-355G4five hundred and sixty-fivesix hundred and seventeensix hundred and fiftythree hundred and fifty-fivefour hundred and eighty
VXXX-400G4six hundred and twenty-ninesix hundred and eighty-sevenseven hundred and twenty-fivefour hundredfive hundred and thirty
VXXX-450G4seven hundred and sixteenseven hundred and eighty-twoeight hundred and twentyfour hundred and fiftysix hundred
VXXX-500G4eight hundredeight hundred and twentynine hundredfive hundredsix hundred and eighty
VXXX-560G4nine hundred and thirtynine hundred and fiftyone thousand and twentyfive hundred and sixtyseven hundred and fifty
VXXX-630G4one thousand and fiftyone thousand and fiftyone thousand one hundred and twentysix hundred and thirtyeight hundred and fifty
VXXX-720G4one thousand and two hundredone thousand and two hundredone thousand and three hundredseven hundred and twentynine hundred and sixty


3. Appearance and installation dimensions

Inverter modelInstallation hole position mmDimensions mmInstallation aperture mmWeight kg
ABHWD
VXXX-R75G4Bseventy-nineone hundred and fifty-fiveone hundred and sixtyeighty-nineone hundred and thirty-fiveØ4
VXXX-1R5G4B
VXXX-2R2G4B
VXXX-3R0G4B
VXXX-4R0G4Beighty-sixone hundred and seventy-fourone hundred and eighty-fourninety-sevenone hundred and forty-fiveØ4
VXXX-5R5G4B
VXXX-7R5G4Bone hundred and thirty-onetwo hundred and forty-fourtwo hundred and fifty-sevenone hundred and forty-sevenone hundred and ninety-fiveØ6
VXXX-011G4B
VXXX-015G4Bone hundred and forty-sixtwo hundred and ninety-eightthree hundred and twentyone hundred and seventytwo hundred and sixteenØ6
VXXX-018G4B
VXXX-022G4B
VXXX-030G4one hundred and twentythree hundred and eighty-fourfour hundredtwo hundredtwo hundred and thirtyØ7
VXXX-037G4
VXXX-045G4two hundredfour hundred and ninety-threefive hundred and tentwo hundred and sixtytwo hundred and sixty-twoØ7
VXXX-055G4
VXXX-075G4two hundredfive hundred and eighty-threesix hundredthree hundredtwo hundred and eighty-fiveØ9
VXXX-090G4
VXXX-110G4
VXXX-132G4two hundred and fiftyseven hundred and fifty-fiveseven hundred and eightyfour hundredthree hundred and fortyØ12
VXXX-160G4
VXXX-185G4
VXXX-200G4three hundred and fiftyeight hundred and seventy-twonine hundredfour hundred and fiftythree hundred and sixty-twoØ12
VXXX-220G4
VXXX-250G4three hundred and sixtynine hundred and twenty-twonine hundred and fiftyfive hundredthree hundred and sixty-twoØ12
VXXX-280G4
VXXX-315G4four hundred and fiftyone thousand and fifteenone thousand and fiftysix hundred and fiftythree hundred and seventy-twoØ13
VXXX-355G4
VXXX-400G4five hundredone thousand three hundred and fifteenone thousand three hundred and fiftyseven hundredthree hundred and eightyØ14
VXXX-450G4
VXXX-500G4
VXXX-560G4six hundredone thousand four hundred and sixtyone thousand and five hundrednine hundredfour hundredØ14
VXXX-630G4
VXXX-720G4


4. Wiring of main circuit and control circuit

image

Figure 1-3 Three phase 380V~480V standard wiring diagram


Panel operation

1. Panel operation instructions

The VXXX series frequency converter can perform parameter operation, status monitoring, and control through the LED operation panel.


2. Introduction to LED operation panel

Using the operation panel, the frequency converter can be operated for parameter setting/modification, working status monitoring, and operation control (start, stop).

The appearance and operation key names of the operation panel are shown in the following figure:


image

Figure 3-1 Schematic diagram of the operation panel


2.1 Function indicator lights

In the table belowimageThe indicator light is on;imageIndicates that the light is off.imageIndicates flashing

Indicator light statusStatus description
RUN running indicator light

image

RUN

Lamp off: Shutdown

image

RUN

Light on: Running
LOCAL/REMOT
Running instruction indicator light

image

LOCAL/ REMOT

Lamp off: panel control

image

LOCAL/ REMOT

Lamp on: Terminal control

image

LOCAL/ REMOT

Flashing: Communication Control
REV forward and reverse indicator light

image

REV

Lamp off: running in forward direction

image

REV

Light on: Reverse operation
ALM
Tuning/torque control/fault indicator light

image

ALM

Lamp off: normal operation

image

ALM

Lamp on: Torque control mode

image

ALM

Slow flashing: tuning state (once per second)

image

ALM

Flash: Fault state (4 times/second)


2.2. Keyboard button function

pressButton nameButton Function
PROGProgramming keysEnter or exit from the first level menu.
ENETERconfirm buttonStep by step enter the menu screen and confirm the set parameters.
imageIncremental keyThe increment of data or parameters.
imageDecreasing keyThe decreasing of data or parameters.
SHIFTShift keyUnder the shutdown display interface and operation display interface, display parameters can be cyclically selected; When modifying parameters, you can choose the modification bit of the parameter.
RUNRun keyUnder the start stop control mode of the "operation panel", it is used for running operations.
STOPStop/ResetWhen in operation, pressing this key can stop the running operation, which is constrained by parameter P7-02; When in a fault alarm state, it can be used for reset operation.
MF.KMulti functional selection keySwitch between the selected functions based on the set value of P7-01.


2.3 Parameter viewing and modification methods

The operation panel of VXXX frequency converter adopts a three-level menu structure for parameter setting and other operations. The three-level menus are:

  • 1) Functional parameter group (first level menu)

  • 2) Parameters (secondary menu)

  • 3) Parameter setting values (three-level menu)


After entering each level of the menu, when the display flashes, you can press the ▲ key, ▼ keyimageUse the key to make modifications. The operation process is shown in the following figure:


image

The three-level menu operation flowchart will display the parameters


a) When operating the third level menu, you can press the PRG key or ENETER key to return to the second level menu. The difference between the two is:

Press the ENTER key to save the set parameters and return to the secondary menu, automatically transitioning to the next parameter; Pressing the PRG key means discarding the current parameter modification and directly returning to the secondary menu of the current parameter number.


b) In the third level menu state, if the parameter does not have a flashing bit, it means that the parameter cannot be modified. Possible reasons include:

(1) This parameter is non modifiable, such as frequency converter type, actual detection parameters, operation record parameters, etc.

(2) This parameter cannot be modified during operation and can only be modified after shutdown.


2.4 Parameter Composition

parameter groupFunctional DescriptionInstructions
P0 ~ PP
A0~ AC
Basic ParametersOperating instructions, frequency instructions, motor parameters, control mode, AI/AO characteristic calibration, optimization control and other parameters.
U0Monitoring parameter groupDisplay of basic monitoring parameters for frequency converters.


3. Panel tray opening size

image

Panel tray hole size diagram



Functional parameter table

The user password for the frequency converter is only used to lock the panel operation. After setting the password, when reading and writing parameters through the keyboard, password verification is required every time the user exits the operation and needs to re-enter; During communication operations, read and write operations can be performed directly without using a password (except for PP and PF groups). The parameter menu in user customized parameter mode is not password protected.


Group P and Group A are basic functional parameters, while Group U is a monitoring functional parameter. The symbol explanations in the parameter table are as follows:

  • ”The set value of this parameter can be changed when the frequency converter is in both shutdown and operation states;

  • ”The set value of this parameter cannot be changed when the frequency converter is in operation;

  • ”The value of this parameter is the actual detection record value and cannot be changed;

  • * ": This parameter is a" manufacturer parameter "and is only set by the manufacturer. Users are prohibited from operating it;


1. Basic functional parameter summary table

parameternameset the scopefactory defaultchange
P0 basic functional group
P0-00GP type1: G-type (constant torque load model)
2: P-type (fan, pump type load models)
Model determination
P0-01The first motor
Control method
0: Speed sensorless vector control (SVC)
1: Vector Control with Speed Sensor (FVC)
2: V/F control
two
P0-02Operation instruction selection0: Operation panel
1: Terminal
2: Communication
0
P0-03Main frequency instruction
Input selection
0: Number setting (no memory in case of power failure)
1: Numerical setting (power-off memory)
2:AI1
3:AI2
4: Panel potentiometer
5: Pulse setting (DI5)
6: Multi segment instruction
7: Simple PLC
8:PID
9: Communication given
four
P0-04Auxiliary frequency
Command input selection
Same as P0-03 (main frequency command input selection)0
P0-05Auxiliary frequency during superposition
Instruction range selection
0: Relative to maximum frequency
1: Relative to the main frequency command
0
P0-06Auxiliary frequency during superposition
Instruction Range
0%~150%100%
P0-07Frequency instruction superposition selectionPosition: Frequency command selection 0: Main frequency command
1: Main and auxiliary operation results (operation relationship determined by ten digits)
2: Switching between main frequency command and auxiliary frequency command
3: Switching between main frequency instruction and main/auxiliary operation results
4: Switching between auxiliary frequency instruction and main/auxiliary operation results in ten digits: frequency instruction main/auxiliary operation relationship
0: Primary+Secondary
1: Main auxiliary
2: The maximum value of both
3: The minimum value of the two
00
P0-08preset frequency0.00Hz~maximum frequency (P0-10)50.00Hz
P0-09running direction0: Default direction of operation
1: Run in the opposite direction to the default direction
0
P0-10maximum frequency50.00Hz~500.00Hz50.00Hz
P0-11Upper limit frequency instruction selection0: P0-12 setting
1:AI1
2:AI2
3:AI3
4: Pulse setting
5: Communication given
0
P0-12upper frequency limitLower limit frequency P0-14~maximum frequency P0-1050.00Hz
P0-13Upper frequency offset0.00Hz~Maximum frequency P0-100.00Hz
P0-14lower cutoff frequency0.00Hz~upper limit frequency P0-120.00Hz
P0-15carrier frequencyModel determinationModel determination
P0-16carrier frequency
Adjust with temperature
0: No
1: Yes, it is
one
P0-17Acceleration time 10.00s~650.00s(P0-19=2)
0.0s~6500.0s(P0-19=1)
0s~65000s(P0-19=0)
Model determination
P0-18Deceleration time 10.00s~650.00s(P0-19=2)
0.0s~6500.0s(P0-19=1)
0s~65000s(P0-19=0)
Model determination
P0-19Acceleration and deceleration time unit0: 1 second
1: 0.1 seconds
2: 0.01 seconds
one
P0-21Auxiliary frequency during superposition
Instruction bias frequency
0.00Hz~Maximum frequency P0-100.00Hz
P0-22Frequency command resolution1:0.1Hz 2:0.01Hztwo
P0-23Digital frequency setting
Shutdown memory selection
0: No memory
1: Memory
0
P0-24Selection of motor parameter group0: Motor parameter group 1
1: Motor parameter group 2
0
P0-25Acceleration
Reference frequency
0: Maximum frequency (P0-10)
1: Set frequency
2:100Hz
0
P0-26Run time frequency instruction
P/DOWN benchmark
0: Operating frequency
1: Set frequency
0
P0-27Running instruction bundling
Main frequency instruction selection
Position: Operation panel binding frequency source selection
0: No binding
1: Digital frequency setting
2:AI1
3:AI2
4:AI3
5: Pulse setting (DI5)
6: Multi speed
7: Simple PLC
8:PID
9: Communication given
Ten digit: Terminal binding frequency source selection
Hundred digit: Communication binding frequency source selection
0000
P0-28Communication protocol selection0: Modbus protocol
1: Profibus DP, CANopen, Profinet, EtherCAT protocols
0
P1 group first motor parameter group
P1-00Motor type selection0: Ordinary asynchronous motor
2: Variable frequency synchronous motor (contact manufacturer)
0
P1-01Rated power of motor0.1kW~1000.0kWModel determination
P1-02Rated voltage of motor1V~2000VModel determination
P1-03Rated current of motor0.01A~655.35A (inverter power ≤ 55kW)
0.1A~6553.5A (inverter power ≤ 55kW)
Model determination
P1-04Rated frequency of motor0.01Hz~maximum frequencyModel determination
P1-05Rated speed of motor1rpm~65535rpmModel determination
P1-06Stator resistance of asynchronous motor0.001 Ω~65.535 Ω (frequency converter power ≤ 55kW)
0.0001 Ω~6.5535 Ω (frequency converter power>55kW)
Tuning parameters
P1-07Asynchronous motor rotor resistance0.001 Ω~65.535 Ω (frequency converter power ≤ 55kW)
0.0001 Ω~6.5535 Ω (frequency converter power>55kW)
Tuning parameters
P1-08Leakage inductance of asynchronous motor0.01mH~655.35H (frequency converter power ≤ 55kW)
0.001mH~65.535mH (frequency converter power>55kW)
Tuning parameters
P1-09Asynchronous motor mutual inductance0.1mH~6553.5mH (frequency converter power ≤ 55kW)
0.01mH~655.35H (frequency converter power>55kW)
Tuning parameters
P1-10Asynchronous motor no-load current0.01A~P1-03 (inverter power ≤ 55kW)
0.1A~P1-03 (inverter power>55kW)
Tuning parameters
P1-27encoder line count1~65535one thousand and twenty-four
P1-28Speed fbk sel0: ABZ incremental encoder
2: Rotating Transformer
0
P1-30ABZ incremental encoder
AB phase sequence
0: Positive
1: Reverse direction
0
P1-34Number of poles of rotary transformer1~65535one
P1-36Speed feedback PG disconnection
Detection Time
0.0s: No action
0.1s~10.0s


P1-37Tuning selection0: No operation
1: Parameter tuning of the static part of asynchronous machine
2: Asynchronous machine dynamic complete tuning
3: Asynchronous machine static complete tuning
11: Synchronize complete tuning
0
P2 group first motor vector control parameter group
P2-00Speed loop proportional gain 11~100thirty
P2-01Speed loop integration time 10.01s~10.00s0.50s
P2-02Switching frequency 10.00~P2-055.00Hz
P2-03Speed loop proportional gain 21~100twenty
P2-04Speed loop integration time 20.01s~10.00s1.00s
P2-05Switching frequency 2P2-02~Maximum frequency10.00Hz
P2-06Vector control slip gain50%~200%100%
P2-07SVC speed
Feedback filtering time
0.000s~0.100s0.015s
P2-09Under speed control mode
Selection of torque upper limit command
0: Parameter P2-10 setting
1:AI1
2:AI2
3:AI3
4: Pulse (DI5)
5: Communication given
6:MIN(AI1,AI2)
7:MAX(AI1,AI2)
The full range of options 1-7 corresponds to P2-10
0
P2-10Numerical setting of torque upper limit under speed control mode0.0%~200.0%150%
P2-11Under speed control mode
Torque upper limit command selection (power generation)
0: Parameter P2-10 setting (without distinguishing between electric and power generation)
1:AI1
2:AI2
3:AI3
4: PULSE pulse setting
5: Communication given
6:MIN(AI1,AI2)
7:MAX(AI1,AI2)
8: Parameter P2-12 setting
The full range of options 1-7 corresponds to P2-12
0
P2-12Under speed control mode
Torque upper limit digital setting (power generation)
0.0% ~ 200.0%150%
P2-13Excitation regulation
Proportional gain
0~60000two thousand
P2-15Torque regulation
Proportional gain
0~60000two thousand
P2-16Torque regulation
Integral gain
0~60000one thousand and three hundred
P2-17Integral attribute of speed loopIndividual position: Integral separation
0: Invalid
1: Effective
0
P2-21Maximum in the weak magnetic region
Torque coefficient
50~200%100%
P2-22power generation capacity
Restricted enablement
0: Invalid
1: Effective throughout the entire process
2: Constant speed effectiveness
3: Deceleration takes effect
0
P3 group V/F control parameter group
P3-00V/F curve setting0: Straight line V/F
1: Multi point V/F
2: Square V/F
3: 1.2 square V/F
4: 1.4 square V/F
6: 1.6 square V/F
8: 1.8 square V/F
9: Reserved
10: V/F complete separation mode
11: V/F semi separation mode
0
P3-01Torque increase0.0%: (Automatic torque boost)
0.1%~30.0%
Model determination
P3-02Torque increase cut-off frequency0.00Hz~maximum frequency50.00Hz
P3-03Multi point V/F frequency point 10.00Hz~ P3-050.00Hz
P3-04Multi point V/F voltage point 10.0%~100.0%0%
P3-05Multi point V/F frequency point 2P3-03~P3-070.00Hz
P3-06Multi point V/F voltage point 20.0%~100.0%0%
P3-07Multi point V/F frequency point 3P3-05~Rated frequency of motor (P1-04)0.00Hz
P3-08Multi point V/F voltage point 30.0%~100.0%0%
P3-10V/F overexcitation gain0~200sixty-four
P3-11V/F oscillation suppression gain0~100forty
P3-13Voltage source separated by V/F0: Numerical setting (P3-14)
1:AI1
2:AI2
3:AI3
4: PULSE pulse setting (DI5)
5: Multi segment instruction
6: Simple PLC
7:PID
8: Communication given
Note: 100.0% corresponds to the rated voltage of the motor
0
P3-14Voltage separated by V/F
Number setting
0V~Rated voltage of motor0V
P3-15Voltage separated by V/F
accelerate time
0.0s~1000.0s
Note: Refers to the time it takes for 0V to change to the rated voltage of the motor
0.0s
P3-16Voltage separated by V/F
deceleration time
0.0s~1000.0s
Note: Refers to the time it takes for 0V to change to the rated voltage of the motor
0.0s
P3-17V/F separation
Selection of shutdown mode
0: Frequency/voltage independently reduced to 0
1: After reducing the voltage to 0, the frequency decreases again
0
P3-18Overcurrent stall action current50~200%150%
P3-19Enable overcurrent stall0: Invalid
1: Effective
one
P3-20Overcurrent stall suppression gain0~100twenty
P3-21Double speed overcurrent stall action
Current compensation coefficient
50~200%50%
P3-22Overvoltage stall action voltageThree phase 380~480V models: 30.0V~800.0V
Three phase 200~240V model: 30.0V~800.0V

P3-23Overpressure stall enable0: Invalid
1: Effective
one
P3-24Overpressure stall
Suppress frequency gain
0~100thirty
P3-25Overpressure stall
Suppress voltage gain
0~100thirty
P3-26Maximum overvoltage stall
Rising frequency limit
0~50Hz5Hz
P4 input terminal parameter group
P4-00DI1 terminal function selection0: No functionality
1: Forward running FWD or running command
2: Reverse running REV or forward and reverse running direction
3: Three line operation control
4: Forward turning jog (F JOG)
5: Reverse Jog (R JOG)
6: Terminal UP
7: Terminal Down
8: Free Parking
9: Fault reset (RESET)
10: Pause operation
11: External fault normally open input
12: Multi segment instruction terminal 1
13: Multi segment instruction terminal 2
14: Multi segment instruction terminal 3
15: Multi segment instruction terminal 4
16: Acceleration and deceleration time selection terminal 1
17: Acceleration and deceleration time selection terminal 2
18: Frequency command switching
19: UP/DOWN reset (terminals, keyboard)
20: Control command switching terminal 1
21: Acceleration and deceleration are prohibited
22: PID pause
23: Simple PLC state reset
24: Swing frequency pause
25: Counter input
26: Counter reset
27: Length Count Input
28: Length reset
29: Torque control prohibited
30: Pulse frequency input (only valid for DI5)
31: Reserved
32: Immediate DC braking
33: External fault normally closed input
34: Frequency modification enable
35: PID action direction is reversed
36: External parking terminal 1
one
P4-01DI2 terminal function selectiontwo
P4-02DI3 terminal function selectionthree
P4-03DI4 terminal function selectiontwelve
P4-04DI5 terminal function selectionthirteen
P4-05DI6 terminal function selection0
P4-06DI7 terminal function selection (expansion board)37: Control command switching terminal 2
38: PID points suspended
39: Switching between main frequency and preset frequency
40: Switching between auxiliary frequency and preset frequency
41: Motor terminal selection function
42: Reserved
43: PID parameter switching
44: User defined fault 1
45: User defined fault 2
46: Switching between speed control and torque control
47: Emergency stop
48: External parking terminal 2
49: Deceleration DC braking
50: This run time is reset to zero
51: Two wire/three wire switching
52: Reverse frequency prohibition
53-59: Reserved
0
P4-07DI8 terminal function selection (expansion board)0
P4-08DI9 terminal function selection (expansion board)0
P4-09DI10 terminal function selection (expansion board)0
P4-10DI filtering time0.000s~1.000s0.010s
P4-11Terminal command method0: Two line type 1
1: Two line type 2
2: Three line type 1
3: Three line type 2
0
P4-12Terminal UP/DOWN
rate of change
0.001Hz/s~65.535Hz/s1.00Hz/s
P4-13AI curve 1 minimum input0.00V~P4-150.00V
P4-14AI curve 1 minimum input
Corresponding settings
-100.0%~+100.0%0%
P4-15AI curve 1 maximum inputP4-13~+10.00V10.00V
P4-16AI curve 1 maximum input
Corresponding settings
-100.0%~+100.0%100%
P4-17AI1 filtering time0.00s~10.00s0.10s
P4-18AI curve 2 minimum input0.00V~P4-200.00V
P4-19AI curve 2 minimum input
Corresponding settings
-100.0%~+100.0%0%
P4-20AI curve 2 maximum inputP4-18~+10.00V10.00V
P4-21AI curve 2 maximum input
Corresponding settings
-100.0%~+100.0%100%
P4-22AI2 filtering time0.00s~10.00s0.10s
P4-23AI Curve 3 Minimum Input-10.00V~P4-25-10.00V
P4-24AI Curve 3 Minimum Input
Corresponding settings
-100.0%~+100.0%-100.0%
P4-25AI curve 3 maximum inputP4-23~+10.00V10.00V
P4-26AI curve 3 maximum input
Corresponding settings
-100.0%~+100.0%100%
P4-27AI3 filtering time0.00s~10.00s0.10s
P4-28Minimum frequency of pulse input0.00kHz~P4-300.00kHz
P4-29Minimum input frequency of pulse
Corresponding settings
-100.0%~100.0%0%
P4-30Maximum input frequency of pulseP4-28~100.00kHz50.00kHz
P4-31Maximum input frequency of pulse
Corresponding settings
-100.0%~100.0%100%
P4-32Pulse filtering time0.00s~10.00s0.10s
P4-33AI curve selectionIndividual position: AI1 curve selection
1: Curve 1 (2 points, see P4-13~P4-16)
2: Curve 2 (2 points, see P4-18~P4-21)
3: Curve 3 (2 points, see P4-23~P4-26)
4: Curve 4 (4 points, see A6-00~A6-07)
5: Curve 5 (4 points, see A6-08~A6-15)
Tenth digit: AI2 curve selection, as above
Hundred digit: AI3 curve selection, as above
three hundred and twenty-one
P4-34AI below minimum input setting
Choose a specific option
Position: AI1 is below the minimum input setting selection
0: Corresponding minimum input setting
1:0.0%
Ten digit: AI2 is lower than the minimum input setting selection, as above
Hundred digit: AI3 below the minimum input setting selection, as above
000
P4-35DI1 delay time0.0s~3600.0s0.0s
P4-36DI2 delay time0.0s~3600.0s0.0s
P4-37DI3 delay time0.0s~3600.0s0.0s
P4-38DI terminal effective mode
Choose 1
0: High level effective
1: Low level effective
Position: DI1
Ten digits: DI2
Hundred digit: DI3
Thousand digits: DI4
10000 positions: DI5
00000
P4-39DI terminal effective mode
Choose 2
0: High level effective
1: Low level effective bits: DI6
Tenth digit: DI7
Hundred digits: DI8
Thousand digits: DI9
10000 positions: DI10
00000
P5 output terminal parameter group
P5-00FM terminal output mode
choice
0: Pulse output (FMP)
1: Switching output (FMR)
0
P5-01FM Function Selection (Set)
Open circuit electrode output terminal
Child)
0: No output
1: Inverter in operation
2: Fault output (for free stop faults)
3: Frequency level detection 1
4: Frequency arrival
5: Zero speed operation (no output during shutdown)
6: Motor overload warning
7: Inverter overload warning
8: Set the record value to arrive
9: The specified record value has been reached
10: Length reached
11: Simple PLC cycle completion
12: Accumulated running time reached
13: Under frequency limitation
14: Torque limitation
15: Ready for operation
16:AI1>AI2
17: The upper limit frequency has been reached
18: Lower limit frequency reached (no output during shutdown)
0
P5-02Relay 1 Function Selection
(T1A-T1B-T1C)
one
P5-03Relay 2 Function Selection
( T2A-T2B-T2C )
two
P5-04DO1 output function selection19: Under voltage state
20: Communication settings
21: Reserved
22: Reserved
23: Zero speed operation 2 (also output when stopped)
24: Accumulated power on time reached
25: Frequency level detection 2
26: Frequency 1 has arrived
27: Frequency 2 arrived
28: Current 1 arrives
29: Current 2 arrives
30: Scheduled arrival
31: AI1 input exceeds the limit
32: Falling load
33: Running in reverse
34: Zero current state
35: The module temperature has reached
36: Output current exceeds the limit
37: The lower limit frequency has been reached (output even when stopped)
38: Alarm (all faults)
39: Motor overheating
40: The current running time has arrived
41: Fault (free stop fault and under voltage not outputting)
0
P5-05Expansion card DO2 output
Function Selection
four
P5-06FMP output function selection0: Operating frequency
1: Set frequency
2: Output current
3: Motor output torque (absolute value, percentage relative to the motor)
4: Output power
5: Output voltage
6: Pulse input (100.0% corresponds to 100.0kHz)
0
P5-07AO1 output function selection7:AI1
8:AI2
9: Panel potentiometer
10: Length
11: Record numerical values
12: Communication settings
13: Motor speed
14: Output current (100.0% corresponds to 1000.0A)
15: Output voltage (100.0% corresponds to 1000.0V)
16: Motor output torque (actual value, percentage relative to the motor)
FMP output function selection
0
P5-08AO2 output function selectionfour
P5-09FMP output maximum frequency0.01kHz~100.00kHz50.00kHz
P5-10AO1 zero bias coefficient-100.0%~+100.0%0%
P5-11AO1 gain-10.00~+10.00one
P5-12AO2 zero bias coefficient-100.0%~+100.0%0%
P5-13AO2 gain-10.00~+10.00one
P5-17FM output delay time0.0s~3600.0s0.0s
P5-18RELAY1 output
delay time
0.0s~3600.0s0.0s
P5-19RELAY2 output
delay time
0.0s~3600.0s0.0s
P5-20DO1 output delay time0.0s~3600.0s0.0s
P5-21DO2 output delay time0.0s~3600.0s0.0s
P5-22DO output terminal is valid
Status selection
0: Positive Logic
1: Anti logical position: FMR
Tenth digit: RELAY1
Hundreds: RELAY2
Thousand positions: DO1
10000 positions: DO2
00000
P6 group start stop control parameter group
P6-00Startup method0: Directly start
1: Speed tracking restart
2: Pre excitation start (AC asynchronous machine)
3: SVC Quick Start
0
P6-01Speed tracking method0: Starting from the shutdown frequency
1: Starting from the power frequency
2: Starting from the maximum frequency
0
P6-02Speed tracking speed1~100twenty
P6-03Startup frequency0.00Hz~10.00Hz0.00Hz
P6-04Start frequency holding time0.0s~100.0s0.0s
P6-05Start DC braking current/pre excitation current0%~100%50%
P6-06Start DC braking time/pre excitation time0.0s~100.0s0.0s
P6-07Acceleration and deceleration methods0: Linear acceleration and deceleration
1: Static S-curve
2: Dynamic S-curve acceleration and deceleration
0
P6-08Starting segment of S-curve
Time proportion
0.0%~(100.0%-P6-09)30%
P6-09End segment of S-curve
Time proportion
0.0%~(100.0%-P6-08)30%
P6-10shutdown method0: Slow down parking 1: Free parking0
P6-11Shutdown DC brake
Starting frequency
0.00Hz~maximum frequency0.00Hz
P6-12Shutdown DC brake
waiting time
0.0s~100.0s0.0s
P6-13Shutdown DC brake current0%~100%50%
P6-14Shutdown DC braking time0.0s~100.0s0.0s
P6-15Brake utilization rate0%~100%100%
P6-18Speed tracking current magnitude30%~200%Model determination
P6-21Demagnetization time
(SVC is effective)
0.00~5.00sModel determination
P6-23Overexcitation selection0: Not effective
1: Only deceleration takes effect
2: Effective throughout the entire process
0
P6-24Overexcitation suppression current value0~150%100%
P6-25Overexcitation gain1.00~2.50one point two five
P7 keyboard and display parameter group
P7-00Digital tube missing picture inspection enable0~10
P7-01MF. K key function selection0: MF. K is invalid
1: Switching between operation panel command channel and remote command channel (terminal command channel or communication command channel)
2: Forward and reverse switching
3: Forward turning jog
4: Reverse jog
0
P7-02STOP/RESET
Key function
0: The STOP/RES key shutdown function is only valid in keyboard operation mode
1: The STOP/RES button shutdown function is valid in any operating mode
one
P7-03LED1 operation
Display parameter 1
0000~FFFF
Bit00: Operating frequency 1 (Hz)
Bit01: Set frequency (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI input status
Bit08: DO output status
Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V)
Bit11: AI3 voltage (V)
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID setting
1F
P7-04LED1 operation
Display parameter 2
0000~FFFF
Bit00: PID feedback
Bit01: PLC Stage
Bit02: PULSE input pulse frequency kHz
Bit03: Operating frequency 2 (Hz)
Bit04: Remaining running time
Bit05: AI1 pre calibration voltage (V)
Bit06: AI2 pre calibration voltage (V)
Bit07: Voltage before AI3 calibration (V)
Bit08: Motor speed
Bit09: Current power on time (Hour)
Bit10: Current running time (Min)
Bit11: Pulse input frequency (Hz)
Bit12: Communication settings
Bit13: Encoder feedback speed (Hz)
Bit14: Main frequency X display (Hz)
Bit15: Auxiliary frequency Y display (Hz)
0
P7-05LED1 shutdown display parameters0000~FFFF
Bit00: Set frequency (Hz)
Bit01: Bus voltage (V)
Bit02: DI input status
Bit03: DO output status
Bit04: AI1 voltage (V)
Bit05: AI2 voltage (V)
Bit06: AI3 voltage (V)
Bit07: Count value
Bit08: Length value
Bit09: PLC Stage
Bit10: Load speed
Bit11: PID setting
Bit12: PULSE input pulse frequency kHz
thirty-three
P7-06Load transmission ratio0.001~65.000two point nine two
P7-07Inverter module
Temperature of radiator
-20℃ ~120℃-
P7-08Product Number--
P7-09Accumulated running time0h~65535h-
P7-10Performance version number--
P7-11Function version number--
P7-12load speed
Display decimal place
Number of decimal points: U0-14
0:0 decimal places
1: One decimal place
2: Two decimal places
Ten digits: U0-19/U0-29 decimal points
1: One decimal place
2: Two decimal places
twenty
P7-13Accumulated power on time0~65535 hours-
P7-14Accumulated power consumption0~65535 degrees-
P7-17LED2 shutdown display parametersU0-00~U0-75two
P7-18LED2 operation display parametersU0-00~U0-75two
P8 auxiliary function parameter group
P8-00Jogging operating frequency0.00Hz~maximum frequency2.00Hz
P8-01Jogging acceleration time0.0s~6500.0s20.0s
P8-02Jogging deceleration time0.0s~6500.0s20.0s
P8-03Acceleration time 20.00s~650.00s ( P0-19=2 )
0.0s~6500.0s ( P0-19=1 )
0s~65000s ( P0-19=0 )
Model determination
P8-04Deceleration time 20.00s~650.00s ( P0-19=2 )
0.0s~6500.0s ( P0-19=1 )
0s~65000s ( P0-19=0 )
Model determination
P8-05Acceleration time 30.00s~650.00s ( P0-19=2 )
0.0s~6500.0s ( P0-19=1 )
0s~65000s ( P0-19=0 )
Model determination
P8-06Deceleration time 30.00s~650.00s ( P0-19=2 )
0.0s~6500.0s ( P0-19=1 )
0s~65000s ( P0-19=0 )
Model determination
P8-07Acceleration time 40.00s~650.00s ( P0-19=2 )
0.0s~6500.0s ( P0-19=1 )
0s~65000s ( P0-19=0 )
0.0s
P8-08Deceleration time 40.00s~650.00s ( P0-19=2 )
0.0s~6500.0s ( P0-19=1 )
0s~65000s ( P0-19=0 )
0.0s
P8-09Received data gain (frequency)-10.00~10.00one
P8-10Jump frequency 20.00Hz~maximum frequency0.00Hz
P8-11Jump frequency amplitude0.00Hz~maximum frequency0.00Hz
P8-12Dead time of forward and reverse rotation0.0s~3000.0s0.0s
P8-13Reverse frequency prohibition0: Invalid 1: Valid0
P8-14Set the operating mode with a frequency lower than the lower limit frequency0: Running at the lower limit frequency
1: Shutdown
2: Zero speed operation
0
P8-15Sag rate0.00%~100.00%0%
P8-16Set the cumulative power on arrival time0h~65000h0h
P8-17Set the cumulative running arrival time0h~65000h0h
P8-18Activate protection selection0: Not protected 1: Protected0
P8-19Frequency detection value 10.00Hz~maximum frequency50.00Hz
P8-20Frequency detection lag rate 10.0%~100.0% (FDT1 level)5%
P8-21Frequency reaches the detected amplitude0.0%~100.0% (maximum frequency)0%
P8-22Is the jumping frequency effective during acceleration and deceleration0: Invalid
1: Effective
0
P8-25Switching frequency points between acceleration time 1 and acceleration time 20.00Hz~maximum frequency0.00Hz
P8-26Switching frequency points between deceleration time 1 and deceleration time 20.00Hz~maximum frequency0.00Hz
P8-27Terminal jog priority0: Invalid 1: Valid0
P8-28Frequency detection value 20.00Hz~maximum frequency50.00Hz
P8-29Frequency detection lag rate 20.0%~100.0% (FDT2 level)5%
P8-30Any frequency of arrival
Detection value 1
0.00Hz~maximum frequency50.00Hz
P8-31Any frequency of arrival
Detection amplitude 1
0.0%~100.0% (maximum frequency)0%
P8-32Any frequency of arrival
Detection value 2
0.00Hz~maximum frequency50.00Hz
P8-33Any frequency of arrival
Detection amplitude 2
0.0%~100.0% (maximum frequency)0%
P8-34Zero current detection level0.0%~300.0%
100.0% corresponds to the rated current of the motor
5%
P8-35Zero current detection
delay time
0.01s~600.00s0.10s
P8-36Output current exceeds the limit value0.0% (not detected)
0.1%~300.0% (rated current of motor)
200%
P8-37Output current exceeds the limit
Detecting delay time
0.00s~600.00s0.00s
P8-38Any current reaching 10.0%~300.0% (rated current of motor)100%
P8-39Arrive arbitrarily
Current amplitude 1
0.0%~300.0% (rated current of motor)0%
P8-40Any current reaching 20.0%~300.0% (rated current of motor)100%
P8-41Arrive arbitrarily
Current amplitude 2
0.0%~300.0% (rated current of motor)0%
P8-42Timer function selection0: Invalid 1: Valid0
P8-43Timed running time selection0: P8-44 setting
1:AI1
2:AI2
3:AI3
Analog input range corresponds to P8-44
0
P8-44Timed running time0.0Min~6500.0Min0.0Min
P8-45AI1 input voltage
Lower limit of protection value
0.00V~P8-463.10V
P8-46AI1 input voltage
Protection value upper limit
P8-45~10.00V6.80V
P8-47The module temperature has reached0℃ ~100℃75℃
P8-48Cooling fan control0: Fan running during operation
1: The fan keeps running
0
P8-49Wake up frequencySleep frequency (P8-51)~
Maximum frequency (P0-10)
0.00Hz
P8-50Wake up delay time0.0s~6500.0s0.0s
P8-51Sleep frequency0.00Hz~wake-up frequency (P8-49)0.00Hz
P8-52Sleep delay time0.0s~6500.0s0.0s
P8-53Arrival time of this run0.0~6500.0 minutes0.0Min
P8-54Output power correction coefficient0.00%~200.0%100%
P8-55Emergency stop deceleration time0~6553.5Model determination
P9 Fault and Protection Parameter Group
P9-00Selection of motor overload protection0: Prohibit 1: Allowone
P9-01Motor overload protection gain0.20~10.00one
P9-02Motor overload warning coefficient50%~100%80%
P9-03Overvoltage stall gain0~100thirty
P9-04Overvoltage stall protection voltage650V~800V770V
P9-07Selection of ground short circuit protectionPosition: Selection of short-circuit protection for power on to ground
0: Invalid 1: Valid
Ten digit: Selection of ground short circuit protection before operation
0: Invalid 1: Valid
01
P9-08Braking unit action
starting voltage
Three phase 380~480V models: 330.0V~800.0V
Three phase 200~240V model: 330.0V~800.0V

P9-09Number of automatic fault resets0~200
P9-10During the automatic fault reset period
Fault DO action selection
0: No action
1: Action
0
P9-11Fault automatic reset waiting
time
0.1s~100.0s1.0s
P9-12Input phase loss contactor
Suction protection selection
Position: Input phase loss protection selection
0: Prohibit input phase loss protection
1: Protection when both software and hardware input phase loss conditions are met simultaneously
2: Protect as long as the software input phase loss condition is met
3: Protect as long as the hardware input phase loss condition is met
Ten digit: contactor suction protection selection
0: Prohibit 1: Allow
eleven
P9-13Phase loss protection selectionPosition: Output phase loss protection selection
0: Prohibit 1: Allow
Ten digit: Selection of output phase loss protection before operation
0: Prohibit 1: Allow
01
P9-14First fault type0: No malfunction
1: Reserved
2: Accelerated overcurrent
3: Deceleration overcurrent
4: Constant speed overcurrent
5: Accelerated overvoltage
6: Deceleration overvoltage
7: Constant speed overvoltage
8: Buffer resistor overload
9: Undervoltage
10: Inverter overload
11: Motor overload
12: Input phase loss
13: Output phase loss
14: Module overheating
15: External malfunction
16: Communication abnormality
17: Abnormal contactor
18: Abnormal current detection
19: Abnormal motor tuning
20: Encoder/PG card abnormality
21: Parameter read/write exception
22: Hardware abnormality of frequency converter
23: Motor short circuit to ground
24: Reserved
25: Reserved
26: The running time has arrived
27: User defined fault 1
28: User defined fault 2
29: The power on time has arrived
30: Load shedding
31: PID feedback lost during runtime
40: Fast current limiting timeout
41: Switching motors during operation
42: Excessive speed deviation
43: Motor overspeed
45: Motor overheating
51: Initial position error
55: Slave failure during master-slave control
-
P9-15Second fault type-
P9-16Third fault type-
P9-17Third time (most recent)
Frequency during malfunction
0.00Hz~655.35Hz0.00Hz
P9-18Third time (most recent)
Current during malfunction
0.00A~655.35A0.00A
P9-19Third time (most recent)
Bus voltage during malfunction
0.0V~6553.5V0.0V
P9-20Third time (most recent)
Input terminal status during malfunction
0~99990
P9-21Third time (most recent)
Output terminal status during malfunction
0~99990
P9-22Third time (most recent)
Inverter status during malfunction
0~655350
P9-23Third time (most recent)
Power on time during malfunction
0s~65535s0s
P9-24Third time (most recent)
Running time during malfunction
0.0s~6553.5s0.0s
P9-27Frequency during the second malfunction0.00Hz~655.35Hz0.00Hz
P9-28Current during the second fault0.00A~655.35A0.00A
P9-29Bus voltage during the second fault0.0V~6553.5V0.0V
P9-30During the second malfunction
Input terminal status
0~99990
P9-31During the second malfunction
Output terminal status
0~99990
P9-32During the second malfunction
Inverter status
0~655350
P9-33Power on time during the second malfunction0s~65535s0s
P9-34Running time during the second malfunction0.0s~6553.5s0.0s
P9-37Frequency during the first malfunction0.00Hz~655.35Hz0.00Hz
P9-38Current during the first malfunction0.00A~655.35A0.00A
P9-39Bus voltage during the first malfunction0.0V~6553.5V0.0V
P9-40During the first malfunction
Input terminal status
0~99990
P9-41During the first malfunction
Output terminal status
0~99990
P9-42During the first malfunction
Inverter status
0~655350
P9-43Power on time during the first malfunction0s~65535s0s
P9-44Running time during the first malfunction0.0s~6553.5s0.0s
P9-47Fault protection action selection 1Position: Motor overload (Err11)
0: Free Parking
1: Stop the machine according to the shutdown method
2: Continue running
Ten digits: Input missing phase (Err12)
Hundred bit: Output phase loss (Err13)
Thousand digit: External fault (Err15)
Ten thousand digits: Communication abnormality (Err16)
00000
P9-48Fault protection action selection 2Position: Encoder/PG card abnormal (Err20) 0: Free parking
Ten digits: Parameter read/write exception (Err21)
0: Free Parking
1: Stop the machine according to the shutdown method
Hundred digit: Action selection for frequency converter overload fault (Err10)
0: Free shutdown
1: Reduced operation
Thousand position: Motor overheating (Err45)
Ten thousand digits: The running time has reached (Err26)
00000
P9-49Fault protection
Action selection 3
Individual position: User defined fault 1 (27)
0: Free Parking
1: Stop the machine according to the shutdown method
2: Continue running
Ten digits: User defined fault 2 (28)
0: Free Parking
1: Stop the machine according to the shutdown method
2: Continue running
Hundred digits: Power on time reached (29)
0: Free Parking
1: Stop the machine according to the shutdown method
2: Continue running
Thousand positions: Load shedding (30)
0: Free Parking
1: Slow down and stop
2: Jump directly to 7% of the rated frequency of the motor to continue running, and automatically return to the set frequency when there is no load drop
Ten thousand bits: PID feedback lost during runtime (31)
0: Free Parking
1: Stop the machine according to the shutdown method
2: Continue running
00000
P9-50Fault protection action
Choose 4
Position: Excessive speed deviation (42)
0: Free Parking
1: Stop the machine according to the shutdown method
2: Continue running
Tenth digit: Motor overspeed (43)
Hundred digit: Initial position error (51)
00000
P9-54Continue operation in case of malfunction
Frequency selection
0: Run at the current operating frequency
1: Run at the set frequency
2: Operate at the upper limit frequency
3: Operate at the lower limit frequency
4: Operating at an abnormal backup frequency
0
P9-55Abnormal backup frequency0.0%~100.0%
(100.0% corresponds to maximum frequency P0-10)
100%
P9-56Motor temperature sensor type0: No temperature sensor
1:PT100
2:PT1000
0
P9-57Motor overheat protection threshold0℃ ~200℃110℃
P9-58Motor overheating warning threshold0℃ ~200℃90℃
P9-59Instant stop function selection0: Invalid
1: Bus voltage constant control
2: Slow down and stop the machine
3: Vibration suppression
0
P9-60Instantly stop and continuously restore voltage80%~100%85%
P9-61Instant non-stop voltage recovery
judge the time
0.0~100.0s0.5S
P9-62Instantaneous non-stop action voltage60%~100%80%
P9-63Load drop protection selection0: Invalid
1: Effective
0
P9-64Load drop detection level0.0~100.0%10%
P9-65Load drop detection time0.0~60.0s1.0s
P9-67Speed detection value0.0%~50.0% (maximum frequency)20%
P9-68Speed detection time0.0s: No detection
0.1~60.0s
1.0s
P9-69Detection value for excessive speed deviation0.0%~50.0% (maximum frequency)20%
P9-70Detection time for excessive speed deviation0.0s: No detection
0.1~60.0s
5.0s
P9-71Instant non-stop gain Kp0~100forty
P9-72Instant non-stop integration coefficient Ki0~100thirty
P9-73Instant stop non-stop action deceleration time0~300.0s20.0s
PA group PID functional parameter group
PA-00PID given source0: PA-01 setting
1:AI1
2:AI2
3:AI3
4: Pulse setting (DI5)
5: Communication given
6: Multi segment instruction given
0
PA-01PID value given0.0%~100.0%50%
PA-02PID feedback source0:AI1
1:AI2
2:AI3
3:AI1-AI2
4: Pulse setting (DI5)
5: Communication given
6:AI1+AI2
7:MAX(|AI1|,|AI2|)
8:MIN(|AI1|,|AI2|)
0
PA-03PID action direction0: Positive effect 1: Negative effect0
PA-04PID given feedback range0~65535one thousand
PA-05Proportional gain KP10.0~1000.0twenty
PA-06Integral time TI10.01s~10.00s2.00s
PA-07Differential time TD10.000s~10.000s0.000s
PA-08PID inversion cut-off frequency0.00~maximum frequency0.00Hz
PA-09PID deviation limit0.0%~100.0%0%
PA-10PID differential limiting0.00%~100.00%0.10%
PA-11PID given change time0.00~650.00s0.00s
PA-12PID feedback filtering time0.00~60.00s0.00s
PA-13PID output filtering time0.00~60.00s0.00s
PA-14retain--
PA-15Proportional gain KP20~1000.0twenty
PA-16Integral time TI20.01s~10.00s2.00s
PA-17Differential time TD20.000s~10.000s0.000s
PA-18PID parameter switching conditions0: Do not switch
1: Switching through DI terminal
2: Automatically switch based on deviation
3: Automatically switch based on operating frequency
0
PA-19PID parameter switching deviation 10.0%~PA-2020%
PA-20PID parameter switching deviation 2PA-19~100.0%80%
PA-21PID initial value0.0%~100.0%0%
PA-22PID initial value retention time0.00~650.00s0.00s
PA-25PID integral attributeIndividual position: Integral separation
0: Invalid 1: Valid
Ten digits: whether to stop integrating after outputting to the limit value
0: Continue to accumulate points 1: Stop accumulating points
00
PA-26PID feedback loss detection value0.0%: Feedback loss without judgment
0.1%~100.0%
0%
PA-27PID feedback loss
Detection Time
0.0s~20.0s0.0s
PA-28PID shutdown calculation0: Shutdown without calculation
1: Calculation during shutdown
0
PC group multi segment instructions, simple PLC parameter group
PC-00Multi segment instruction 0-100.0%~100.0%0%
PC-01Multi segment instruction 1-100.0%~100.0%0%
PC-02Multi segment instruction 2-100.0%~100.0%0%
PC-03Multi segment instruction 3-100.0%~100.0%0%
PC-04Multi segment instruction 4-100.0%~100.0%0%
PC-05Multi segment instruction 5-100.0%~100.0%0%
PC-06Multi segment instruction 6-100.0%~100.0%0%
PC-07Multi segment instruction 7-100.0%~100.0%0%
PC-08Multi segment instruction 8-100.0%~100.0%0%
PC-09Multi segment instruction 9-100.0%~100.0%0%
PC-10Multi segment instruction 10-100.0%~100.0%0%
PC-11Multi segment instruction 11-100.0%~100.0%0%
PC-12Multi segment instruction 12-100.0%~100.0%0%
PC-13Multi segment instruction 13-100.0%~100.0%0%
PC-14Multi segment instruction 14-100.0%~100.0%0%
PC-15Multi segment instruction 15-100.0%~100.0%0%
PC-16Simple PLC operation mode0: Shutdown at the end of a single run
1: Maintain the final value at the end of a single run
2: Continuously looping
0
PC-17Simple PLC loses power
Memory selection
Position: Power down memory selection
0: No memory after power failure
1: Power off memory
Ten digit: Shutdown Memory Selection
0: Shutdown without memory
1: Shutdown memory
00
PC-18Simple PLC Stage 0 Running Time0.0s(h)~6553.5s(h)0.0s(h)
PC-19Simple PLC segment 0
Acceleration and deceleration time selection
0~30
PC-20Simple PLC first stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-21Simple PLC Section 1
Acceleration and deceleration time selection
0~30
PC-22Simple PLC second stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-23Simplified PLC, Section 2
Acceleration and deceleration time selection
0~30
PC-24Simple PLC third stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-25Simple PLC Section 3
Acceleration and deceleration time selection
0~30
PC-26Simple PLC fourth stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-27Simple PLC, Section 4
Acceleration and deceleration time selection
0~30
PC-28Simple PLC 5th stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-29Simple PLC 5th paragraph
Acceleration and deceleration time selection
0~30
PC-30Simple PLC 6th stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-31Simplified PLC Section 6
Acceleration and deceleration time selection
0~30
PC-32Simple PLC 7th stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-33Simple PLC segment 7
Acceleration and deceleration time selection
0~30
PC-34Simple PLC 8th stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-35Simple PLC segment 8
Acceleration and deceleration time selection
0~30
PC-36Simple PLC 9th stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-37Simple PLC segment 9
Acceleration and deceleration time selection
0~30
PC-38Simple PLC 10th running time0.0s(h)~6553.5s(h)0.0s(h)
PC-39Simple PLC Section 10
Acceleration and deceleration time selection
0~30
PC-40Simple PLC 11th stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-41Simple PLC 11th paragraph
Acceleration and deceleration time selection
0~30
PC-42Simple PLC 12th segment running time0.0s(h)~6553.5s(h)0.0s(h)
PC-43Simple PLC 12th paragraph
Acceleration and deceleration time selection
0~30
PC-4413th running time of simple PLC0.0s(h)~6553.5s(h)0.0s(h)
PC-45Simple PLC 13th paragraph
Acceleration and deceleration time selection
0~30
PC-4614th running time of simple PLC0.0s(h)~6553.5s(h)0.0s(h)
PC-47Simple PLC Section 14
Acceleration and deceleration time selection
0~30
PC-48Simple PLC 15th stage running time0.0s(h)~6553.5s(h)0.0s(h)
PC-49Simple PLC paragraph 15
Acceleration and deceleration time selection
0~30
PC-50Simple PLC operating time unit0: s (seconds) 1: h (hours)0
PC-51Multi segment instruction 0 given method0: Given parameter PC-00
1:AI1
2:AI2
3:AI3
4: Pulse
5:PID
6: Given preset frequency (P0-08), UP/DOWN can be modified
0
Pd group communication parameter group
Pd-00Baud ratePosition: MODBUS
0:300BPS
1:600BPS
2:1200BPS
3:2400BPS
4:4800BPS
5:9600BPS
6:19200BPS
7:38400BPS
8:57600BPS
9:115200BPS
Ten digits: Profibus DP
0:115200BPs
1:208300BPs
2:256000BPs
3:512000Bps
Hundred digits: reserved
Thousand bits: CANlink baud rate
0:20
1:50
2:100
3:125
4:250
5:500
6:1M
five thousand and five
Pd-01MODBUS data format0: No verification (8-N-2)
1: Even verification (8-E-1)
2: Odd verification (8-O-1)
3: No verification (8-N-1) (MODBUS valid)
0
Pd-02localhost0: Broadcast address
1~247(Modbus、Profibus-DP、CANlink、Profinet、EtherCAT 有效 )
one
Pd-03MODBUS response delay0~20ms (MODBUS valid)two
Pd-04Serial communication timeout0.0: Invalid
0.1~60.0s(Modbus、Profibus-DP、CANopen、Profinet、EtherCAT有效 )
zero
Pd-05Data transmission format selectionPosition: Modbus
0: Non standard Modbus protocol
1: Standard Modbus protocol
十位 :Profibus-DP、CANopen、Profinet、EtherCAT
0: PPO1 format
1: PPO2 format
2: PPO3 format
3: PPO5 format
thirty-one
Pd-06Communication reading current resolution0:0.01A (effective when ≤ 55kW)
1:0.1A
0
Pd-08Profibus DP, CANopen, Profinet, EtherCAT communication interruption detection time0.0s: Invalid
0.1~60.0s
0
PE group water supply parameter group
PE-00Sleep pressure deviation0.0~PE-040%
PE-01Sleep rate0~10, unit 5Hz/S02
PE-02Sleep frequency0.00Hz~maximum frequency (P0-10)2.00Hz
PE-03holding time000.0~999.9Stwo
PE-04Awaken pressure deviation0.0~PA-015%
PE-05Wake up delay time000.0~999.9Szero
PE-06Sleep down time000.0~100.0Stwo
PE-07Selection of water shortage detection methods0: Not detected
1: Current mode
2: Pressure mode
3: Both types are used
0
PE-08Water shortage detection pressure0.0~PA-010.5%
PE-09Water shortage detection frequency0.00Hz~maximum frequency (P0-10)5.00Hz
PE-10Water shortage detection time000.0~999.9Sfive
PE-11Water shortage detection current0.01~Rated current of the set modelzero point zero one
PE-12Automatic water shortage fault
Reset interval time
001~100Sfifteen
PE-13PID high limit alarm set value0.0%~100%one hundred
PE-14PID high limit alarm detection time000~200S, Set to 0 without alarmzero
PE-15PID low limit alarm set value0.0%~100%zero
PE-16PID low limit alarm detection time000~200S, Set to 0 without alarmzero
PE-17Power on automatic operation selection0: Close 1: Open0
PE-18Automatic running delay time00.1~100Sone
PE-19Antifreeze function selection0: Close 1: Open0
PE-20Antifreeze cycle000~9999S, When set to 0, run continuously at the anti freezing operating frequency0
PE-21Antifreeze operation time000~9999Ssixty
PE-22Antifreeze operating frequency0.00~30.00Hzten
PP group function code management parameter group
PP-00user password0~655350
PP-01parameter initialization0: No operation
01: Restore factory parameters, excluding motor parameters
02: Clear record information
04: Backup the current parameters of the user
501: Restore user backup parameters
0
PP-02Function parameter group display selectionPosition: U group display selection
0: Not displayed
1: Display
Ten digits: Group A display selection
0: Not displayed
1: Display
eleven
PP-03Personalized parameter group display selectionIndividual position: User customized parameter group display selection
0: Not displayed
1: Display
Ten: User changes parameter group display selection
0: Not displayed
1: Display
00
PP-04Parameter modification attribute0: modifiable
1: Cannot be modified
0


2. Monitoring parameter summary table

parameternameminimum unitMailing Address
U0 group monitoring parameter table
U0-00Operating frequency (Hz)0.01Hz7000H
U0-01Set frequency (Hz)0.01Hz7001H
U0-02Bus voltage (V)0.1V7002H
U0-03Output voltage (V)1V7003H
U0-04Output current (A)0.01A7004H
U0-05Output power (kW)0.1kW7005H
U0-06Output torque (%)0.1%7006H
U0-07DI input statusone7007H
U0-08DO output statusone7008H
U0-09AI1 voltage (V)0.01V7009H
U0-10AI2 voltage (V)/current (mA)0.01V/0.01mA700AH
U0-11AI3 voltage (V)0.01V700BH
U0-12count valueone700CH
U0-13length valueone700DH
U0-14load speed1RPM700EH
U0-15PID settingone700FH
U0-16PID feedbackone7010H
U0-17PLC stageone7011H
U0-18Input pulse frequency (Hz)0.01kHz7012H
U0-19Feedback speed (Hz)0.01Hz7013H
U0-20Remaining running time0.1Min7014H
U0-21AI1 pre calibration voltage0.001V7015H
U0-22AI2 pre calibration voltage (V)/current (mA)0.001V/0.01mA7016H
U0-23AI3 pre calibration voltage0.001V7017H
U0-24Motor speed1RPM7018H
U0-25Current power on time1Min7019H
U0-26Current running time0.1Min701AH
U0-27Input pulse frequency1Hz701BH
U0-28Communication settings0.01%701CH
U0-29Encoder feedback speed0.01Hz701DH
U0-30Main frequency display0.01Hz701EH
U0-31Auxiliary frequency display0.01Hz701FH
U0-32View any memory address valueone7020H
U0-34Motor temperature value1℃7022H
U0-35Target torque (%)0.1%7023H
U0-36Rotating positionone7024H
U0-37Power factor perspective0.1°7025H
U0-38ABZ positionone7026H
U0-39V/F separation target voltage1V7027H
U0-40V/F separation output voltage1V7028H
U0-41Direct display of DI input statusone7029H
U0-42Visual display of DO output statusone702AH
U0-43DI Function Status Visual Display 1 (Functions 01-40)one702BH
U0-44DI Function Status Visual Display 2 (Functions 41-80)one702CH
U0-45Fault informationone702DH
U0-58Z-signal counterone703AH
U0-59Set frequency (%)0.01%703BH
U0-60Operating frequency (%)0.01%703CH
U0-61Inverter statusone703DH
U0-62Current fault codeone703EH
U0-63Point to point host communication sends torque values0.01%703FH
U0-64Number of stationsone7040H
U0-65Torque upper limit0.1%7041H
U0-73Motor serial number0: Motor 1
1: Motor 2
7049H
U0-74Inverter output torque0.1%704AH
U0-76Low cumulative electricity consumption0.1 degrees704CH
U0-77Accumulated high electricity consumption1 degree704DH
U0-78linear velocity1m/Min704EH


Fault diagnosis and countermeasures

1. Safety precautions

danger

  • It is strictly prohibited to connect wires while the power is turned on. Please make sure to keep all circuit breakers in the OFF state. Otherwise, there is a risk of electric shock.


Warning

  • Please ensure that the frequency converter is grounded in accordance with local regulations. Otherwise, there may be a risk of electric shock or fire hazard.

  • Do not disassemble the casing or touch the internal circuit of the frequency converter when it is powered on. Otherwise, there is a risk of electric shock.

  • Fault inspection must be carried out by professionals, and non professionals are strictly prohibited from inspecting, maintaining, and repairing the frequency converter. Otherwise, there may be a risk of electric shock or fire hazard.

  • When installing the frequency converter in a closed cabinet or casing, please use a cooling fan or cooling air conditioner to fully cool it, so as to keep the intake temperature of the frequency converter below 50 ℃. Otherwise, it may cause overheating or fire.

  • Please tighten all screws according to the specified torque. Otherwise, there may be a risk of fire or electric shock.

  • Please confirm that the input voltage of the product is within the rated voltage range on the nameplate, otherwise there may be a risk of electric shock or fire.


Attention

  • When performing installation work, please cover the upper part of the inverter with a cloth or paper to prevent metal shavings, oil, water, etc. from entering the interior of the inverter during drilling. If foreign objects enter the interior of the frequency converter, it may cause the frequency converter to malfunction.

  • After finishing the homework, please remove these cloths or papers. If it continues to be covered, it will deteriorate the ventilation and cause abnormal heating of the frequency converter.

  • When operating the frequency converter, please follow the steps specified for electrostatic discharge (ESD) prevention measures, otherwise the internal circuits of the frequency converter may be damaged due to static electricity.


2. Adjustment guide before trial operation of frequency converter

1) Open loop vector control mode (P0-01=0 factory default value)

This control mode is used to control the speed and torque of the motor in applications where there is no encoder speed feedback. In this control mode, self-learning of motor parameters is required to achieve automatic tuning of motor parameters.

Problems and malfunctionsCountermeasures
Overload or overcurrent fault reported during motor start-up process
  • The motor parameters (P1-01~P1-05) are set according to the motor nameplate.

  • Perform motor parameter tuning (P1-37), and if conditions permit, it is best to perform dynamic and complete motor tuning.

Slow torque or speed response below 5Hz, motor vibration
  • To improve the response of torque and speed, it is necessary to strengthen the proportional adjustment of the speed loop (P2-00 increases the set value by 10 units) or reduce the integration time of the speed loop (P2-01 decreases by 0.05 units);

  • If there is vibration, it is necessary to weaken P2-00 and increase the parameter value of P2-01.

Slow torque or speed response above 5Hz, motor vibration.
  • To improve the response of torque and speed, it is necessary to strengthen the proportional adjustment of the speed loop (P2-03 increases the set value by 10 units) or reduce the integration time of the speed loop (P2-04 decreases by 0.05 units);

  • If there is vibration, it is necessary to weaken P2-03 and increase the parameter value of P2-04.

Low speed accuracy
  • When the speed deviation of the motor under load is too large, the vector slip compensation gain (P2-06) needs to be increased or decreased by 10%.

Large speed fluctuations
  • When there is abnormal fluctuation in motor speed, the speed filtering time (P2-07) can be appropriately increased in units of 0.001s.

The motor has loud noise
  • Appropriately increase the carrier frequency value (P0-15), increasing in units of 1.0KHz; (Note: Increasing the carrier frequency of the motor will increase the leakage current)

Insufficient motor torque or output
  • Is the torque upper limit restricted? Increase the torque upper limit (P2-10) in speed mode; Increase torque command in torque mode


2) Closed loop vector control mode (P0-01=1)

This mode is used in applications where the motor has encoder speed feedback. It is necessary to correctly set the number of encoder lines, encoder type, and signal direction to achieve automatic tuning of motor parameters.

Problems and malfunctionsCountermeasures
Start reporting overcurrent or overload fault
  • Correctly set the number, type, and direction of encoder lines

Overload or overcurrent fault reported during motor rotation
  • The motor parameters (P1-01~P1-05) are set according to the motor nameplate.

  • Perform motor parameter tuning (P1-37), and if possible, it is best to perform dynamic and complete motor tuning.

Slow torque or speed response below 5Hz, motor vibration
  • To improve the response of torque and speed, it is necessary to strengthen the proportional adjustment of the speed loop (P2-00 increases the set value by 10 units) or reduce the integration time of the speed loop (P2-01 decreases by 0.05 units);

  • If there is vibration, it is necessary to reduce the values of the P2-00 and P2-01 parameters.

Slow torque or speed response above 5Hz, motor vibration.
  • To improve the response of torque and speed, it is necessary to strengthen the proportional adjustment of the speed loop (P2-03 increases the set value by 10 units) or reduce the integration time of the speed loop (P2-04 decreases by 0.05 units);

  • If there is vibration, it is necessary to reduce the values of the P2-03 and P2-04 parameters.

Large speed fluctuations
  • When there is abnormal fluctuation in motor speed, the speed filtering time (P2-07) can be appropriately increased in units of 0.001s.

The motor has loud noise
  • Appropriately increase the carrier frequency value (P0-15), increasing in units of 1.0kHz; (Note: Increasing the carrier frequency of the motor will increase the leakage current)

Insufficient motor torque or output
  • Is the torque upper limit restricted? Increase the torque upper limit (P2-10) in speed mode; Increase torque command in torque mode


3) V/F control mode (P0-01=2)

This mode is used in applications where the motor does not have encoder speed feedback, and is not sensitive to motor parameters. Only the rated voltage and rated frequency values of the motor need to be set correctly.

Problems and malfunctionsCountermeasures
Motor oscillation during operation
  • Increase the oscillation suppression parameter (P3-11) in units of 10 (maximum adjusted to 100);

High power starting alarm overcurrent
  • Reduce torque boost (P3-01), adjust in units of 0.5%;

Excessive current during operation
  • Correctly set the rated voltage (P1-02) and rated frequency (P1-04) of the motor;

  • Reduce torque boost (P3-01), adjust in units of 0.5%;

The motor has loud noise
  • Appropriately increase the carrier frequency value (P0-15), increasing in units of 1.0kHz; (Note: Increasing the carrier frequency of the motor will increase the leakage current)

Sudden unloading overload reports overvoltage, deceleration reports overvoltage
  • Confirm that the overvoltage stall enable (P3-23) is set to the enable state; Increase the overvoltage stall gain (P3-24/P3-25, factory 30) in units of 10 (maximum adjusted to 100);

  • Reduce the overvoltage stall action voltage (P3-22 factory 770V) in units of 10V (minimum adjusted to 700V);

Sudden overload reporting overcurrent, acceleration reporting overcurrent
  • Increase the overcurrent stall gain (P3-20 factory 20) in units of 10 (maximum adjusted to 100);

  • Reduce the overcurrent stall action current (P3-18 factory 150%) by 10% (minimum adjusted to 50%);


3. Fault alarm and countermeasures

During the use of the frequency converter, the following types of faults may be encountered. Please refer to the following methods for simple fault analysis:

Fault name and
panel display
Troubleshooting of the cause of the malfunctionFault handling measures
Accelerated overcurrent
Err02
The output circuit of the frequency converter is grounded or short circuited
  • Eliminate peripheral faults and check if there is a short circuit in the motor or interruption contactor

Control mode is FVC or SVC without parameter identification
  • Set motor parameters according to the motor nameplate and identify motor parameters

Rapid acceleration condition, acceleration time set too short
  • Increase acceleration time

Inappropriate setting for overcurrent stall suppression
  • Confirm that the overcurrent stall suppression function (P3-19) has been enabled;

  • The set value of overcurrent stall action current (P3-18) is too high. It is recommended to adjust it within 120% to 150%;

  • The overcurrent stall suppression gain (P3-20) is set too small, and it is recommended to adjust it within 20 to 40;

Manual torque increase or inappropriate V/F curve
  • Adjust manual torque or V/F curve

Start the rotating motor
  • Choose to start with speed tracking or wait for the motor to stop before starting again

Affected by external interference
  • Check the historical fault records. If the current value during the fault is far from reaching the overcurrent point value, it is necessary to search for the interference source. If there are no other sources of interference, it may be a problem with the driver board or Hall devices.

Deceleration overcurrent
Err03
The output circuit of the frequency converter is grounded or short circuited
  • Eliminate peripheral faults and check whether the motor has a short circuit or open circuit

Control mode is FVC or SVC without parameter identification
  • Set motor parameters according to the motor nameplate and identify motor parameters

Rapid deceleration condition, deceleration time set too short
  • Increase deceleration time

Inappropriate setting for overcurrent stall suppression
  • Confirm that the overcurrent stall suppression function (P3-19) has been enabled;

  • The set value of overcurrent stall action current (P3-18) is too high. It is recommended to adjust it within 120% to 150%;

  • The overcurrent stall suppression gain (P3-20) is set too small, and it is recommended to adjust it within 20 to 40;

No braking unit or braking resistor added
  • Add braking unit and resistor

Affected by external interference
  • Check the historical fault records. If the current value during the fault is far from reaching the overcurrent point value, it is necessary to search for the interference source. If there are no other sources of interference, it may be a problem with the driver board or Hall devices.

Constant speed overcurrent
Err04
The output circuit of the frequency converter is grounded or short circuited
  • Eliminate peripheral faults and check whether the motor has a short circuit or open circuit

Control mode is FVC or SVC without parameter identification
  • Set motor parameters according to the motor nameplate and identify motor parameters

Inappropriate setting for overcurrent stall suppression
  • Confirm that the overcurrent stall suppression function (P3-19) has been enabled;

  • The set value of overcurrent stall action current (P3-18) is too high. It is recommended to adjust it within 120% to 150%;

  • The overcurrent stall suppression gain (P3-20) is set too small, and it is recommended to adjust it within 20 to 40;

The selection of frequency converter is too small
  • In a stable operating state, if the operating current exceeds the rated current of the motor or the rated output current of the frequency converter, please choose a frequency converter with a higher power level

Affected by external interference
  • Check the historical fault records. If the current value during the fault is far from reaching the overcurrent point value, it is necessary to search for the interference source. If there are no other sources of interference, it may be a problem with the driver board or Hall devices.

Accelerated overvoltage
Err05
Input voltage is too high
  • Adjust the voltage to the normal range

During the acceleration process, there is an external force dragging the motor to run
  • Cancel additional power or install braking resistors

Inappropriate overvoltage suppression setting
  • Confirm that the overvoltage suppression function (P3-23) has been enabled;

  • The set value of the overvoltage suppression action voltage (P3-22) is too high. It is recommended to adjust it within 770V~700V;

  • The overvoltage suppression gain (P3-24) is set too small. It is recommended to adjust it within 30 to 50;

No brake unit or brake resistor installed
  • Install brake unit and resistor

The acceleration time is too short
  • Increase acceleration time

Deceleration overvoltage
Err06
Inappropriate overvoltage suppression setting
  • Confirm that the overvoltage suppression function (P3-23) has been enabled;

  • The set value of the overvoltage suppression action voltage (P3-22) is too high. It is recommended to adjust it within 770V~700V;

  • The overvoltage suppression gain (P3-24) is set too small. It is recommended to adjust it within 30 to 50;

During the deceleration process, there is an external force dragging the motor to operate
  • Cancel additional power or install braking resistors

The deceleration time is too short
  • Increase deceleration time

No brake unit or brake resistor installed
  • Install brake unit and resistor

Constant speed overvoltage
Err07
Inappropriate overvoltage suppression setting
  • Confirm that the overvoltage suppression function (P3-23) has been enabled;

  • The set value of the overvoltage suppression action voltage (P3-22) is too high. It is recommended to adjust it within 770V~700V;

  • The overvoltage suppression frequency gain (P3-24) is set too small. It is recommended to adjust it within 30 to 50;

  • The maximum rise frequency for overvoltage suppression (P3-26) is set too low, and it is recommended to adjust it within 5-20Hz;

There is external force dragging the motor during operation
  • Cancel additional power or install braking resistors

Buffer power failure
Err08
The bus voltage fluctuates up and down at the undervoltage point
  • Seeking technical support

Undervoltage fault
Err09
Instantaneous power outage
  • Enable the instantaneous stop function (P9-59) to prevent under voltage faults caused by instantaneous power outages

The input voltage of the frequency converter is not within the range required by the specifications
  • Adjust the voltage to the normal range

Abnormal bus voltage
  • Seeking technical support

Abnormal rectifier bridge, buffer resistor, driver board, and control board
  • Seeking technical support

Inverter overload
Err10
Is the load too large or is there motor stalling
  • Reduce the load and check the motor and mechanical condition

The selection of frequency converter is too small
  • Choose a frequency converter with a higher power level

Motor overload
Err11
Is the setting of motor protection parameter P9-01 appropriate
  • Set this parameter correctly

Is the load too large or is there motor stalling
  • Reduce the load and check the motor and mechanical condition

input phase loss
Err12
The three-phase input power supply is abnormal
  • Check and eliminate problems in the peripheral circuits

Abnormal driving board, lightning protection board, main control board, rectifier bridge
  • Seeking technical support

Output phase loss
Err13
Motor failure
  • Check if the motor is open circuited

The lead from the frequency converter to the motor is abnormal
  • Eliminate peripheral faults

The three-phase output of the frequency converter is unbalanced during the operation of the motor
  • Check if the three-phase winding of the motor is normal and eliminate the fault

Abnormal driver board and IGBT module
  • Seeking technical support

Module overheating
Err14
The ambient temperature is too high
  • Reduce the ambient temperature

Air duct blockage
  • Clean the air duct

Fan damaged
  • Replace the fan

Module thermistor damaged
  • Seeking manufacturer services

Inverter module damaged
  • Seeking manufacturer services

External device malfunction
Err15
Input external fault signals through the multifunctional terminal DI
  • Check the peripheral faults, confirm that the machine is allowed to restart (P8-18), and reset the operation

Input external fault signals through virtual IO function
  • Confirm that the parameters of the A1 virtual IO group are set correctly, reset and run

communication failure
Err16
The upper computer is not working properly
  • Check the wiring of the upper computer

The communication line is abnormal
  • Check the communication connection cable

Communication expansion card P0-28 is not set correctly
  • Correctly set the type of communication expansion card

Communication parameter PD group settings are incorrect
  • Set communication parameters correctly

After completing the above tests, the fault still cannot be eliminated
  • You can try restoring the factory settings.

Contactor failure
Err17
Abnormal driver board and power supply
  • Seeking manufacturer services

Abnormal contactor
  • Seeking manufacturer services

Abnormal lightning protection board
  • Seeking manufacturer services

Current detection fault
Err18
Check for abnormal Hall devices
  • Seeking manufacturer services

Driver board abnormality
  • Seeking manufacturer services

Motor tuning fault
Err19
The motor parameters are not set according to the nameplate
  • Set the motor parameters correctly according to the nameplate

Parameter identification process timed out
  • Check the leads from the frequency converter to the motor


  • Check if the number of encoder wires is set correctly P1-27, and if the signal wires of the encoder are connected correctly and securely

Encoder failure
Err20
Encoder model mismatch
  • Set the encoder type correctly according to the actual situation

Encoder wiring error
  • Detecting PG card power supply and phase sequence

Encoder damaged
  • Replace the encoder

PG card abnormality
  • Replace PG card

EEPROM
Read/write malfunction
Err21
EEPROM chip damaged
  • Seeking manufacturer services

Short circuit fault to ground
Err23
Motor short circuit to ground
  • Replace cables or motors

Accumulated running time
Arrival malfunction
Err26
Accumulated running time reaches the set value
  • Use parameter initialization function to clear record information

user-defined
Fault 1
Err27
Input user-defined fault 1 signal through the multifunctional terminal DI
  • Reset operation

Input user-defined fault 1 signal through virtual IO function
  • Reset operation

user-defined
Fault 2
Err28
Input the signal of user-defined fault 2 through the multifunctional terminal DI
  • Reset operation

Input user-defined fault 2 signal through virtual IO function
  • Reset operation

Accumulated power on time
Arrival malfunction
Err29
Accumulated power on time reaches the set value
  • Use parameter initialization function to clear record information

Load shedding fault
Err30
The operating current of the frequency converter is less than P9-64
  • Confirm whether the load is detached or whether the parameter settings of P9-64 and P9-65 are in line with the actual operating conditions

Run time PID
Feedback loss fault
Err31
PID feedback is less than the set value of PA-26
  • Check the PID feedback signal or set PA-26 to an appropriate value

PID low limit alarm
Err32
PID feedback is less than the set value of PE-15
  • Set PE-15 as an appropriate value

PID high limit alarm
Err33
PID feedback is greater than the set value of PE-13
  • Set PE-13 as an appropriate value

Water shortage alarm
Err34
Operating frequency higher than PE-09 and output current lower than PE-11
  • Set PE-08 and PE-11 to an appropriate value

Operating frequency higher than PE-09 and feedback pressure lower than PE-08
Wave by wave current limiting fault
Err40
Is the load too large or is there motor stalling
  • Reduce the load and check the motor and mechanical condition

The selection of frequency converter is too small
  • Choose a frequency converter with a higher power level

Run time switching
Motor failure
Err41
Change the current motor selection through terminals during the operation of the frequency converter
  • Perform motor switching operation after shutting down the frequency converter

Speed deviation
Excessive malfunction
Err42
Incorrect encoder parameter settings
  • Correctly set encoder parameters

No parameter identification has been carried out
  • Perform motor parameter identification

The detection parameters P9-69 and P9-70 for excessive speed deviation are not set properly
  • Reasonably set detection parameters according to the actual situation

Motor overspeed
fault
Err43
Incorrect encoder parameter settings
  • Correctly set encoder parameters

No parameter identification has been carried out
  • Perform motor parameter identification

The setting of motor overspeed detection parameters P9-67 and P9-68 is unreasonable
  • Reasonably set detection parameters according to the actual situation

Motor overheating fault
Err45
Loose wiring of temperature sensor
  • Check the wiring of the temperature sensor and troubleshoot any issues

Motor temperature is too high
  • Raise the carrier frequency or take other heat dissipation measures to dissipate heat from the motor

Master-slave control
Slave malfunction
Err55
The slave has malfunctioned, check the slave
  • Troubleshooting according to the slave fault code


4. Common faults and their solutions

serial numberFault phenomenonPossible reasonstreatment method
oneNo display when powered onPower grid voltage is absent or too low
  • Check the input power supply

Switching power supply fault on the frequency converter drive board
  • Check if the 24V and 10V output voltages on the control board are normal

The connection between the control board, driver board, and keyboard is broken
  • Re plug and unplug 8-core and 34 core ribbon cables

The buffer resistor of the frequency converter is damaged
  • Seeking manufacturer services

Control board and keyboard malfunction
Damaged rectifier bridge
two

Always displaying when powered on

-A-C-

Poor contact of the wiring between the driver board and the control board
  • Re plug and unplug the 8-core and 28 core ribbon cables

Related components on the control board are damaged
  • Seeking manufacturer services

Motor or motor wire has a short circuit to ground
Hall fault
The voltage of the power grid is too low
threePower on display report
Police display
Err23
Motor or output line short circuited to ground
  • Measure the insulation of the motor and output line with a shaking table

The frequency converter is damaged
  • Seeking manufacturer services

fourPower on frequency converter
Display is normal,
Display after running
-A-C-
And immediately shut down the machine
Fan damage or blockage
  • Replace the fan

fiveFrequent reporting
Err14 (mold)
Block overheating)
Obstacle Err14
The carrier frequency is set too high
  • Reduce carrier frequency (P0-15)

sixInverter operation
rear motor
Do not rotate
Fan damage or air duct blockage
  • Replace the fan and clean the air duct

Internal components of the frequency converter are damaged (thermistor or other)
  • Seeking manufacturer services

Poor contact between the driver board and control board connection
  • Re plug and unplug the connecting wire, confirm that the wiring is secure;

Driver board malfunction
  • Seeking manufacturer services

sevenDI terminal failureParameter setting error
  • Check and reset the relevant parameters of P4 group

External signal error
  • Reconnect the external signal line

OP and+24V jumper loose
  • Reconfirm the OP and+24V jumper wires and ensure they are securely fastened.

Control board malfunction
  • Seeking manufacturer services

eightClosed-loop vector control
Timing, electricity
Machine speed cannot be reached
enhance
Encoder failure
  • Replace the code wheel and reconfirm the wiring

Encoder wiring error or poor contact
  • Reconnect the wires to ensure good contact

nineFrequent frequency converter
Report overcurrent and overcurrent
Pressure fault
Incorrect motor parameter settings
  • Reset motor parameters or perform motor tuning

Inappropriate acceleration and deceleration time
  • Set appropriate acceleration and deceleration times

Load fluctuation
  • Seeking manufacturer services

tenpower on
(or run)
Report Err17
Soft start contactor not engaged
  • Check if the contactor cable is loose

  • Check if the contactor is faulty

  • Check if there is a fault in the 24V power supply of the contactor

  • Seeking manufacturer services